Function Parameters
Detailed instruction of parameters
The counter works with the S1 to S5 terminals when P05.01
to P05.05 is 31
When
the
counter
multi-function output terminals will output the signal of "fixed
counting number arrival" and the counter go on working;
when the counter achieves a setting number, the
multi-function output terminals will output the signal of
"setting counting number arrival", the counter will clear all
numbers and stop to recount before the next pulse.
The given counting value P08.26 should be no more than
the setting counting value P08.25.
The function is illustrated as below:
Setting range of P08.25: P08.26~65535
Setting range of P08.26: 0~P08.25
Pre-set running time of the inverter. When the accumulative
running time achieves the set time, the multi-function digital
output terminals will output the signal of "running time
arrival". Setting range:0~65535min
Number of fault auto-reset attempts: set the fault reset
attempts by selecting this function. If the reset attempts
exceed this set value, the inverter will stop for the fault and
wait to be repaired.
The interval time of the fault reset: The interval between
the time when the fault occurs and the time when the reset
action occurs.
Setting range of P08.28: 0~10
Setting range of P08.29: 0.1~3600.0s
When the output frequency exceeds the corresponding
frequency of "FDT electrical level detection value", the
multi-function digital output terminals will output the signal of
achieves
a
fixed
Default
value
0
number,
the
0
0m
0
1.0s
50.00Hz
Modify
51 - 104