Salicru CV10-002-S2 User Manual page 29

Controlvit cv10 series
Table of Contents

Advertisement

Function
Name
code
before DC
braking
DC braking
P01.11
current
DC braking
P01.12
time
Dead time of
P01.13
FWD/REV
rotation
Switching
between
P01.14
FWD/REV
rotation
Function Parameters
Detailed instruction of parameters
caused by DC braking at high speed.
DC braking current:The value of P01.11 is the percentage
of rated current of inverter. The bigger the DC braking
current is, the greater the braking torque is.
DC braking time: The retention time of DC braking. If the
time is 0, the DC braking is invalid. The inverter will stop at
the set deceleration time.
The setting range of P01.09: 0.00Hz~P00.03
The setting range of P01.10: 0.0~50.0s
The setting range of P01.11: 0.0~100.0%
The setting range of P01.12: 0.0~50.0s
During the procedure of switching FWD/REV rotation, set the
threshold by P01.14, which is as the table below:
Setting range: 0.0~3600.0s
Set the threshold point of the inverter:
0: Switch after zero frequency
1: Switch after the starting frequency
Default
Modify
value
0.0%
0.00s
0.00s
0
29 - 104