Function
Name
code
RO switching
P06.10
on delay time
RO switching
P06.11
off delay time
P06.14
AO output
Lower limit of
P06.17
AO output
Corresponding
P06.18
AO output to
the lower limit
Upper limit of
P06.19
AO output
Corresponding
P06.20
AO output to
the upper limit
42 - 104
Detailed instruction of parameters
The function code defines the corresponding delay time of
the electrical level change during the programmable terminal
switching on and off.
The setting range :0.000~50.000s
0: Running frequency
1: Set frequency
2: Ramp reference frequency
3: Running rotation speed
4: Output current (relative to twice the inverter rated current)
5: Output current (relative to twice the motor rated current)
6: Output voltage
7: Output power
8: Set torque value
9: Output torque
10: Analog AI1 input value
11: Analog AI2 input value
14: MODBUS communication set value 1
15: MODBUS communication set value 2
16~30: Reserved
The above function codes define the relative relationship
between the output value and analog output. When the output
value exceeds the range of set maximum or minimum output, it
will count according to the low-limit or upper-limit output.
When the analog output is current output, 1mA equals to 0.5V.
In different cases, the corresponding analog output of 100%
of the output value is different.
Default
Modify
value
0.000s
0.000s
0
0.0%
0.00V
100.0%
10.00V