Function
Name
code
B frequency
P00.08
command
reference
Combination
P00.09
type of the
setting source
Keypad set
P00.10
frequency
P00.11
ACC time 1
P00.12
DEC time 1
Running
P00.13
direction
selection
Function Parameters
Detailed instruction of parameters
0: Maximum output frequency, 100% of B frequency
setting corresponds to the maximum output frequency
(P00.03)
1: A frequency command, 100% of B frequency setting
corresponds to A frequency setting. Select this setting if it
needs to adjust on the base of A frequency command
0: A, the current frequency setting is A frequency command
1: B, the current frequency setting is B frequency command
2: A+B, the current frequency setting is A frequency
command + B frequency command
3: A-B, the current frequency setting is A frequency
command - B frequency command
4: Max (A, B): The bigger one between A frequency
command and B frequency is the set frequency.
5: Min (A, B): The lower one between A frequency command
and B frequency is the set frequency.
Note: The combination manner can be shifted by P05
(terminal function)
When A and B frequency commands are selected as
"keypad setting", this parameter will be the initial value of
inverter reference frequency
Setting range: 0.00 Hz~P00.03 (the Max. frequency)
ACC time means the time needed if the inverter speeds up
from 0Hz to the Max. output frequency (P00.03).
DEC time means the time needed if the inverter speeds
down from the Max. Output frequency (P00.03) to 0Hz.
CV10 inverters define four groups of ACC/DEC time which
can be selected by P05. The factory default ACC/DEC time
of the inverter is the first group.
Setting range of P00.11 and P00.12:0.0~3600.0s
0: Runs at the default direction, the inverter runs in the
forward direction. FWD/REV indicator is off.
1: Runs at the opposite direction, the inverter runs in the
reverse direction. FWD/REV indicator is on.
Modify the function code to shift the rotation direction of the
motor. This effect equals to the shifting the rotation direction
by adjusting either two of the motor lines (U, V and W). The
motor rotation direction can be changed by QUICK/JOG on
the keypad. Refer to parameter P07.02.
Note: When the function parameter comes back to the
Default
Modify
value
0
0
50.00Hz
Depends
on model
Depends
on model
0
25 - 104