Salicru CV10-002-S2 User Manual page 60

Controlvit cv10 series
Table of Contents

Advertisement

Function
Name
code
Overvoltage
P11.03
stall protection
Overvoltage
P11.04
stall point
Current limit
P11.05
action selection
Automatic
P11.06
current limit
level
Decreasing
P11.07
ratio during
current limit
60 - 104
Detailed instruction of parameters
0:Disabled
1:Enabled
120~150%
The actual increasing ratio is less than the ratio of output frequency
because of the big load during ACC running. It is necessary to take
measures to avoid overcurrent fault and the inverter trips.
During the running of the inverter, this function will detect the output
current and compare it with the limit level defined in P11.06. If it
exceeds the level, the inverter will run at stable frequency in ACC
running, or the inverter will derate to run during the constant running.
If it exceeds the level continuously, the output frequency will keep on
decreasing to the lower limit. If the output current is detected to be
lower than the limit level, the inverter will accelerate to run.
Setting range of P11.05:
0: current limit invalid
1: current limit valid
Setting range of P11.06:50.0~200.0%
Setting range of P11.07:0.00~50.00Hz/s
Default
Modify
value
1
120%
1
160.0%
10.00Hz/s
Function Parameters