Function
Name
code
Detection level of
P11.11
the underload
pre-alarm
Detection time of
P11.12
the underload
pre-alarm
Output terminal
P11.13
action selection
during fault
Local
P14.00
communication
address
P14.01
Baud rate
62 - 104
Detailed instruction of parameters
If the inverter current or the output current is lower than
P11.11, and its lasting time is beyond P11.12, the inverter
will output underload pre-alarm.
Setting range of P11.11: 0~P11.09
Setting range of P11.12: 0.1~60.0s
Select the action of fault output terminals on undervoltage
and fault reset.
0x00~0x11
LED ones:
0: Action under fault undervoltage
1: No action under fault undervoltage
LED tens:
0: Action during the automatic reset
1: No action during the automatic reset
P14 Group Serial communication
The setting range:1~247
When the master is writing the frame, the communication
address of the slave is set to 0; the broadcast address is the
communication address. All slaves on the MODBUS fieldbus
can receive the frame, but the slave doesn't answer.
The communication address of the drive is unique in the
communication net. This is the fundamental for the point to point
communication between the upper monitor and the drive.
Note: The address of the slave cannot set to 0.
Set the digital transmission speed between the upper
monitor and the inverter.
0: 1200BPS
1: 2400BPS
2: 4800BPS
3: 9600BPS
4: 19200BPS
Default
Modify
value
50%
1.0s
0x00
1
4
Function Parameters