Function
Name
code
Switch filter
P05.11
time
Virtual
P05.12
terminals
setting
Terminals
P05.13
control running
mode
Function Parameters
Detailed instruction of parameters
Set the sample filter time of S1~S5 terminals. If the interference is
strong, increase the parameter to avoid the wrong operation.
0.000~1.000s
Enable the input function of virtual terminals at the
communication mode.
0: Virtual terminals is invalid
1: MODBUS communication virtual terminals are valid
Set the operation mode of the terminals control
0: 2-wire control 1, comply the enable with the direction. This
mode is widely used. It determines the rotation direction by the
defined FWD and REV terminals command.
FWD
K1
REV
K2
COM
1: 2-wire control 2; Separate the enable from the direction. FWD
defined by this mode is the enabling one. The direction depends
on the state of the defined REV.
2: 3-wire control 1; SIn is the enabling terminal in this mode, and
the running command is caused by FWD and the direction is
controlled by REV. SIn is normal closed.
Running
FWD
REV
command
OFF
OFF
Stopping
Forward
ON
OFF
running
Reverse
OFF
ON
running
ON
ON
Hold on
Default
Modify
value
0.010s
0
0
37 - 104