Setting 1: Combine input terminal values to create frequency reference (V1, V2, V3 are combined)
With this setting, all three input signals on the AI-A3 option card are added together to create the frequency reference.
When the option card is the source of the frequency reference for the drive, parameter b1-01 must be set to 3. Gain and
bias settings for the frequency reference supplied from AI-A3 can be set using parameters F2-02 and F2-03.
F2-02, F2-03: Analog Input Option Card Gain, Bias
Parameter F2-02 sets the gain and parameter F2-03 sets the bias for the AI-A3 input signal when the card is used in the
combined input signals mode (F2-01 = 1). Both gain and bias are set as a percentage of the maximum output frequency.
No.
F2-02
F2-03
Note: Enabled only when F2-01 = 1.
 F3: Digital Input Card Settings
These parameters set up the drive for operation with the option card DI-A3. This section describes parameters that
govern operation with a digital input option card. Refer to the instruction manual packaged with the option card for
specific details on installation, wiring, input signal level selection, and parameter setup.
F3-01: Digital Input Option Card Input Selection
Determines the type of input for digital option card DI-A3 when o1-03 is set to 0 or 1.
No.
F3-01
Setting 0: BCD, 1% units
Setting 1: BCD, 0.1% units
Setting 2: BCD, 0.01% units
Setting 3: BCD, 1 Hz units
Setting 4: BCD, 0.1 Hz units
Setting 5: BCD, 0.01 Hz units
Setting 6: BCD, special setting (5 digit input), 0.02 Hz units
Setting 7: Binary
The unit and the setting range are determined by F3-03.
F3-03 = 0: 255/100% (-255 to +255)
F3-03 = 1: 4095/100% (-4095 to +4095)
F3-03 = 2: 30000/100% (-33000 to +33000)
Note: BCD input when o1-03 = 2 or 3. Units are determined by o1-03.
F3-03: Digital Input Option DI-A3 Data Length Selection
Determines the number of bits for the option card input that sets the frequency reference.
No.
F3-03
Setting 0: 8 bit
Setting 1: 12 bit
Setting 2: 16 bit
YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual
Parameter Name
Analog Input Option Card Gain
Analog Input Option Card Bias
Parameter Name
Digital Input Option Card Input Selection
Parameter Name
Digital Input Option DI-A3 Data Length Selection
5.6 F: Option Settings
Setting Range
-999.9 to 999.9%
-999.9 to 999.9%
Setting Range
0 to 7
Setting Range
Default
0 to 2
Default
100.0%
0.0%
Default
0
5
2
229