YASKAWA A1000 Technical Manual page 508

High performance vector control drive type: cimr-a series models: 200 v class: 0.55 to 110 kw, 400 v class: 0.55 to 630 kw
Hide thumbs Also See for A1000:
Table of Contents

Advertisement

B.3 Parameter Table
No. (Addr.)
Name
T1-04
Motor Rated Current
(704H)
T1-05
Motor Base Frequency
(705H)
T1-06
Number of Motor Poles
(706H)
T1-07
Motor Base Speed
(707H)
T1-08
PG Number of Pulses Per
(708H)
Revolution
Motor No-Load Current 
T1-09
(709H)
(Stationary Auto-Tuning)
Motor Rated Slip 
T1-10
(70AH)
(Stationary Auto-Tuning)
T1-11
Motor Iron Loss
(70BH)
<6> Default setting value varies by the drive model (o2-04).
<9> Default setting value is dependent on the drive model (o2-04) and the Drive Duty (C6-01).
<10> Default setting is determined by the control mode (A1-02).
<18> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<37> The availability of certain Auto-Tuning methods depends on the control mode selected for the drive.
<38> Default setting value differs depending on the motor code value and motor parameter settings.
T2: PM Motor Auto-Tuning
No. (Addr.)
Name
T2-01
PM Motor Auto-Tuning Mode
(750H)
Selection
<37>
T2-02
PM Motor Code Selection
(751H)
508
V/f
V/f w/PG
OLV/PM
AOLV/PM
Sets the motor rated current as specified on the motor nameplate.
V/f
V/f w/PG
OLV/PM
AOLV/PM
Sets the rated frequency of the motor as specified on the motor nameplate.
V/f
V/f w/PG
OLV/PM
AOLV/PM
Sets the number of motor poles as specified on the motor nameplate.
V/f
V/f w/PG
OLV/PM
AOLV/PM
Sets the rated speed of the motor as specified on the motor nameplate.
V/f
V/f w/PG
OLV/PM
AOLV/PM
Set the number of pulses per revolution for the PG being used (pulse generator or encoder).
V/f
V/f w/PG
OLV/PM
AOLV/PM
Sets the no-load current for the motor.
After setting the motor capacity to T1-02 and the motor rated current to T1-04, this parameter
will automatically display the no-load current for a standard 4 pole YASKAWA motor. Enter the
no-load current as indicated on the motor test report.
V/f
V/f w/PG
OLV/PM
AOLV/PM
Sets the motor rated slip.
After setting the motor capacity to T1-02, this parameter will automatically display the motor
slip for a standard 4 pole YASKAWA motor. Enter the motor slip as indicated on the motor test
report.
V/f
V/f w/PG
OLV/PM
AOLV/PM
Sets the iron loss for determining the Energy Saving coefficient.
The value is set to E2-10 (motor iron loss) set when the power is cycled. If T1-02 is changed, a
default value appropriate for the motor capacity that was entered will appear.
V/f
V/f w/PG
OLV/PM
AOLV/PM
0: PM Motor Parameter Settings
1: PM Stationary Auto-Tuning
2: PM Stationary Auto-Tuning for Stator Resistance
3: Z Pulse Offset Tuning
8: Inertia Tuning
9: ASR Gain Auto-Tuning
11: Back EMF Constant Tuning
13: High Frequency Injection Parameter Tuning
14: PM Rotational Auto-Tuning
Note: 1.The settings of 13 and 14 are not available for models CIMR-A4A0930 and 4A1200.
2. Inertia Tuning and ASR Gain Auto-Tuning might not be available if gears are between
the machine and the motor shaft.
3. For special-purpose motors, YASKAWA recommends Back EMF Constant Tuning
after Stationary Auto-Tuning has been performed. Back EMF Constant Tuning rotates
the motor to measure the actual induction voltage constants, and therefore allows for
more accurate control than Stationary Auto-Tuning alone.
V/f
V/f w/PG
OLV/PM
AOLV/PM
Enter the motor code when using a YASKAWA PM motor. Once the motor code is entered, the
drive automatically sets parameters T2-03 through T2-09. Set T2-10 through T2-14 from the
values on the motor nameplate or from the motor test report. When using a motor that is not
supported motor code or a non-YASKAWA motor, set FFFF here and then adjust the other T2
parameters according the motor nameplate or the motor test report.
YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual
Description
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
Description
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
Setting
Page
Default:
<6>
Min: 10% of drive rated
current
128
Max: 200% of drive
rated current
Default: 50.0 Hz
Min: 0.0 Hz
128
Max: 400.0 Hz
Default: 4
Min: 2
129
Max: 48
-1
Default: 1450 min
-1
Min: 0 min
129
Max: 24000 min
-1
Default: 1024 ppr
Min: 0 ppr
129
Max: 60000 ppr
Default: –
Min: 0 A
129
Max: T1-04
Default: –
Min: 0.00 Hz
129
Max: 20.00 Hz
Default: 14 W
<38>
Min: 0 W
129
Max: 65535 W
Setting
Page
Default: 0
Min: 0
130
Max: 3, 8, 9, 11,13,
14
<10>
Default:
<16>
Min: 0000
130
Max: FFFF