No. (Addr.)
Name
U1-10
Input Terminal Status
(49H)
U1-11
Output Terminal Status
(4AH)
U1-12
Drive Status
(4BH)
U1-13
Terminal A1 Input Level
(4EH)
U1-14
Terminal A2 Input Level
(4FH)
U1-15
Terminal A3 Input Level
(50H)
U1-16
Output Frequency after Soft
(53H)
Starter
U1-17
DI-A3 Input Status
(58H)
U1-18
oPE Fault Parameter
(61H)
YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual
All Modes
Displays the input terminal status.
U1 - 10=
0 0 0 0 0 0 0 0
All Modes
Displays the output terminal status.
U1 - 11=
0 0 0 0 0 0 0 0
All Modes
Displays the drive operation status.
U1 - 12=
0 0 0 0 0 0 0 0
All Modes
Displays the signal level to analog input terminal A1.
All Modes
Displays the signal level to analog input terminal A2.
All Modes
Displays the signal level to analog input terminal A3.
All Modes
Displays output frequency with ramp time and S-curves. Units determined by o1-03.
All Modes
Displays the reference value input from the DI-A3 option card.
Display will appear in hexadecimal as determined by the digital card input selection in F3-01.
3FFFF: Set (1 bit) + sign (1 bit) + 16 bit
All Modes
Displays the parameter number that caused the oPE02 or oPE08 (Operation error).
Description
1
Digital input 1
(terminal S1 enabled)
1
Digital input 2
(terminal S2 enabled)
1
Digital input 3
(terminal S3 enabled)
1
Digital input 4
(terminal S4 enabled)
1
Digital input 5
(terminal S5 enabled)
1
Digital input 6
(terminal S6 enabled)
1
Digital input 7
(terminal S7 enabled)
1
Digital input 8
(terminal S8 enabled)
1
Multi-Function
Digital Output
(terminal M1-M2)
1
Multi-Function
Digital Output
(terminal M3-M4)
1
Multi-Function
Digital Output
(terminal M5-M6)
Not Used
1
Fault Relay Output
(terminal MA-MC closed
MA/MB-MC open)
1
During run
1
During zero-speed
1
During REV
1
During fault reset
signal input
1
During speed agree
1
Drive ready
1
During alarm
detection
1
During fault detection
B.3 Parameter Table
Analog Output
Unit
Page
Level
No signal output
available
No signal output
available
No signal output
available
10 V: 100%
0.1%
(-10 to +10 V)
10 V: 100%
0.1%
(-10 to +10 V)
10 V: 100%
0.1%
(-10 to +10 V)
10 V: Max frequency
0.01 Hz
(-10 to +10 V)
No signal output
available
No signal output
available