5.1 A: Initialization

5.1
A: Initialization
The initialization group contains parameters associated with initial setup of the drive. Parameters involving the display
language, access levels, initialization, and password are located in this group.
 A1: Initialization
A1-00: Language Selection
Selects the display language for the digital operator (option).
Note: This parameter is not reset when the drive is initialized using parameter A1-03.
No.
A1-00
Setting 0: English
Setting 1: Japanese
Setting 2: German
Setting 3: French
Setting 4: Italian
Setting 5: Spanish
Setting 6: Portuguese
Setting 7: Chinese
Setting 8: Czech
Setting 9: Russian
Setting 10: Turkish
Setting 11: Polish
Setting 12: Greek
Note: 1. Settings 8 to 12 can be selected from an LCD operator with version (REV) F or later. The version is listed on the back of the LCD
operator.
2. The setting range is 0 to 7 in models CIMR-A4A0930 and 4A1200.
A1-01: Access Level Selection
Allows or restricts access to drive parameters.
No.
A1-01
Setting 0: Operation only
Allows access and programming of parameters A1-01, A1-04, and Drive Mode.
Allows access to all U monitor parameters.
Does not allow access to Verify Mode, Setup Mode, or Auto-Tuning Mode.
Setting 1: User Parameters
Allows access and programming of parameters A1-00, A1-01, A1-04, and Drive Mode.
Allows access to all U monitor parameters.
Allows access to parameters set in A2-01 to A2-32 in Setup Mode.
Does not allow access to Verify Mode or Auto-Tuning Mode.
Setting 2: Advanced Access Level (A) and Setup Access Level (S)
All parameters can be viewed and edited.
Notes on Parameter Access
• If the drive parameters are password protected by A1-04 and A1-05, parameters A1-01 through A1-03, A1-06, A1-07,
and A2-01 through A2-32 cannot be modified.
• If a digital input terminal programmed for "Program lockout" (H1- = 1B) is enabled, parameter values cannot be
modified, even if A1-01 is set to 1 or 2.
• If parameters are changed via serial communication, then it will not be possible to edit or change parameters settings
with the drive's digital operator until an Enter command is issued to the drive from the serial communication.
142
Parameter Name
Language Selection
Parameter Name
Access Level Selection
YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual
Setting Range
0 to 12
Setting Range
0 to 2
Default
0
Default
2