 Setting 2: Conveyor Application
No.
A1-02
Control Method Selection
C1-01
Acceleration Time 1
C1-02
Deceleration Time 1
C6-01
Duty Rating
L3-04
Stall Prevention Selection during Deceleration
No.
A1-02
Control Method Selection
b1-01
Frequency Reference Selection
b1-02
Run Command Selection
C1-01
Acceleration Time 1
 Setting 3: Exhaust Fan Application
No.
A1-02
Control Method Selection
b1-04
Reverse Operation Selection
C6-01
Duty Selection
E1-03
V/f Pattern Selection
E1-07
Mid Output Frequency
E1-08
Mid Output Frequency Voltage
L2-01
Momentary Power Loss Operation Selection
L3-04
Stall Prevention Selection during Deceleration
No.
b1-01
Frequency Reference Selection
b1-02
Run Command Selection
b1-04
Reverse Operation Selection
b3-01
Speed Search Selection at Start
C1-01
Acceleration Time 1
C1-02
Deceleration Time 1
E1-03
V/f Pattern Selection
 Setting 4: HVAC Fan Application
No.
A1-02
Control Method Selection
b1-04
Reverse Operation Selection
b1-17
Run Command at Power Up
C6-01
Duty Rating
C6-02
Carrier Frequency Selection
H2-03
Terminals P2 Function Selection
L2-01
Momentary Power Loss Operation Selection
L8-03
Overheat Pre-Alarm Operation Selection
L8-38
Carrier Frequency Reduction
No.
b1-01
Frequency Reference Selection
b1-02
Run Command Selection
b1-03
Stopping Method Selection
b1-04
Reverse Operation Selection
C1-01
Acceleration Time 1
C1-02
Deceleration Time 1
C6-02
Carrier Frequency Selection
d2-01
Frequency Reference Upper Limit
YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual
Table 4.8 Conveyor: Parameter Settings
Parameter Name
Table 4.9 Conveyor: User Parameters (A2-01 to A2-16)
Parameter Name
Table 4.10 Exhaust Fan: Parameter Settings
Parameter Name
Table 4.11 Exhaust Fan: User Parameters (A2-01 to A2-16)
Parameter Name
Table 4.12 HVAC Fan: Parameter Settings
Parameter Name
Table 4.13 HVAC Fan: User Parameters (A2-01 to A2-16)
Parameter Name
Default Setting
0: V/f Control
3.0 s
3.0 s
0: Heavy Duty (HD)
1: Enabled
No.
C1-02
Deceleration Time 1
E2-01
Motor Rated Current
L3-04
Stall Prevention Selection during Deceleration
Default Setting
0: V/f Control
1: Reverse Prohibited
1: Normal Duty (ND)
F: V/f Pattern Selection
30.0 Hz
50.0 V
1: Enabled
1: Enabled
No.
E1-07
Mid Output Frequency
E1-08
Mid Output Frequency Voltage
E2-01
Motor Rated Current
H1-05
Multi-Function Digital Input Terminal S5 Function Selection
H1-06
Multi-Function Digital Input Terminal S6 Function Selection
H1-07
Multi-Function Digital Input Terminal S7 Function Selection
L5-01
Number of Auto Restart Attempts
Default Setting
0: V/f Control
1: Reverse Prohibited
1: Run command issued, motor operation start
1: Normal Duty (ND)
3: 8.0 kHz
39: Watt Hour Pulse Output
2: CPU Power Active - Drive will restart if power returns prior to control power supply shut
down.
4: Operation at lower speed
2: Enabled across entire frequency range.
No.
d2-02
Frequency Reference Lower Limit
E1-03
V/f Pattern Selection
E1-04
Max Output Frequency
E2-01
Motor Rated Current
H3-11
Terminal A2 Gain Setting
H3-12
Terminal A2 Input Bias
L2-01
Momentary Power Loss Operation Selection
o4-12
kWh Monitor Initial Value Selection
4.6 Application Selection
Parameter Name
Parameter Name
Parameter Name
4
115

Hide quick links: