Note: Prevent foreign matter such as metal shavings or wire clippings from falling into the drive during installation and project
construction. Failure to comply could result in damage to the drive. Place a temporary cover over the top of the drive during
installation. Remove the temporary cover before startup, as the cover will reduce ventilation and cause the drive to overheat.
External/Face-Mount
1.
Cut an opening in the enclosure panel for the digital operator as shown in
2.
Position the digital operator so the display faces outwards, and mount it to the enclosure panel as shown in
Figure
2.11.
Figure 2.11
Figure 2.12
Figure 2.12 Panel Cut-Out Dimensions (External/Face-Mount Installation)
Internal/Flush-Mount
An internal flush-mount requires an installation support set that must be purchased separately. Contact your YASKAWA
representative to order an installation support set and mounting hardware.
Installation Support Set A.
1.
Cut an opening in the enclosure panel for the digital operator as shown in
2.
Mount the digital operator to the installation support.
3.
Mount the installation support set and digital operator to the enclosure panel.
Figure 2.13
M4 × 10
Phillips truss head screw × 4
(for panel widths between 1 and 1.6)
Note: For environments with a significant amount of dust or other airborne debris, use a gasket between the enclosure panel and the
digital operator.
YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual
Digital Operator
Figure 2.11 External/Face-Mount Installation
Figure 2.13 Internal/Flush Mount Installation
M3 × 6
Phillips recessed
pan head machine screw × 2
Enclosure panel
Unit: mm
22
22
14
Unit: mm
Figure 2.13
Enclosure panel
Digital Operator
Installation Support Set A
M3 × 6
Phillips recessed
pan head machine screw × 2
2.2 Mechanical Installation