YASKAWA A1000 Technical Manual page 259

High performance vector control drive type: cimr-a series models: 200 v class: 0.55 to 110 kw, 400 v class: 0.55 to 630 kw
Hide thumbs Also See for A1000:
Table of Contents

Advertisement

Setting 1: -10 to 10 Vdc
The input level is -10 to 10 Vdc.
Setting 2: 4 to 20 mA
The input level is 4 to 20 mA. Negative input values by negative bias or gain settings will be limited to 0%.
Setting 3: 0 to 20 mA
The input level is 0 to 20 mA. Negative input values by negative bias or gain settings will be limited to 0%.
H3-10: Terminal A2 Function Selection
Determines the function assigned to analog input terminal A2.
on page 260
for a list of functions and descriptions.
No.
H3-10
H3-11, H3-12: Terminal A2 Gain and Bias Setting
Parameter H3-11 sets the level of the input value selected that is equal to 10 Vdc input or 20 mA input to terminal A2.
Parameter H3-12 sets the level of the input value selected that is equal to 0 V, 4 mA or 0 mA input at terminal A2.
Both can be used to adjust the characteristics of the analog input signal to terminal A2. The setting works in the same
way as parameters H3-03 and H3-04 for analog input A1.
No.
H3-11
H3-12
H3-13: Analog Input Filter Time Constant
Parameter H3-13 sets the time constant for a first order filter that will be applied to the analog inputs.
An analog input filter can be used to prevent erratic drive control when a "noisy" analog reference is used. The drive
operation becomes more stable the longer the time programmed, but it becomes less responsive to rapidly changing
analog signals.
No.
H3-13
H3-14: Analog Input Terminal Enable Selection
When one of the multi-function digital input parameters is set for "Analog input enable" (H1- = C), the value set to
H3-14 determines which of the analog input terminals will be enabled or disabled when the input is closed. All analog
input terminals will be enabled all of the time if H1- is not set to C. The terminals other than the one set as the target
are not influenced by input signals.
No.
H3-14
Setting 1: A1 only enabled
Setting 2: A2 only enabled
Setting 3: A1 and A2 only enabled
Setting 4: A3 only enabled
Setting 5: A1 and A3 only enabled
Setting 6: A2 and A3 only enabled
Setting 7: All analog input terminals enabled
YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual
Refer to Setting 1: -10 to 10 Vdc on page
Name
Terminal A2 Function Selection
Name
Terminal A2 Gain Setting
Terminal A2 Bias Setting
Name
Analog Input Filter Time Constant
Name
Analog Input Terminal Enable Selection
257.
Refer to Multi-Function Analog Input Terminal Settings
Setting Range
0 to 32
Setting Range
-999.9 to 999.9%
-999.9 to 999.9%
Setting Range
0.00 to 2.00 s
Setting Range
1 to 7
5.7 H: Terminal Functions
Default
0
Default
100.0%
0.0%
Default
0.03 s
Default
7
5
259