YASKAWA A1000 Technical Manual page 240

High performance vector control drive type: cimr-a series models: 200 v class: 0.55 to 110 kw, 400 v class: 0.55 to 630 kw
Hide thumbs Also See for A1000:
Table of Contents

Advertisement

5.7 H: Terminal Functions
Figure 5.63
shows an operation example of Fast Stop.
Figure 5.63
NOTICE: Rapid deceleration can trigger an overvoltage fault. When faulted, the drive output shuts off, and the motor coasts. To avoid
this uncontrolled motor state and to ensure that the motor stops quickly and safely, set an appropriate Fast Stop time to C1-09.
Setting 16: Motor 2 selection
The drive has the capability to control two induction motors independently. A second motor may be selected using a
multi-function digital input as shown in
Note: The motor 2 selection function cannot be used when PM motor is used.
Figure 5.64
When switching between motor 1 and motor 2, the parameters used to control those motors also change. Below,
Table 5.37
lists the parameters that correspond to each motor.
No.
C1-: Acceleration/Deceleration Time
C3-: Motor Slip Compensation
C4-: Motor Torque Compensation
C5-: Speed Control (ASR)
E1-, E3-: V/f Pattern
E2-, E4-: Motor Parameters
F1- (PG Constant)
Note: 1. When using 2 motors, the motor overload protection selection (oL1) set to L1-01 applies to both motor 1 and motor 2.
2. It is not possible to switch between motor 1 and motor 2 during run. Doing so will trigger the "rUn" alarm.
3. There is a 500 ms delay when switching during CLV control and a 200 ms delay for all other control modes. Wait for at least these
times after switching the motor before issuing the next Run command.
4. The motor 2 selection function cannot be used when PM motor is used.
If a digital output is programmed for "Motor 2 selection" (H2-01, H2-02, or H2-03 = 1C), the output is closed when
motor 2 is selected.
Setting 18: Timer function input
This setting configures a digital input terminal as the input for the timer function. Use this setting combination with the
timer function output (H2- = 12).
Setting 19: PID disable
When the PID function has been enabled by parameter b5-01, it can be indefinitely disabled by closing a digital input.
When the input is released, the drive resumes PID operation. Also refer to
240
Run/Stop
Fast-Stop
H1-
= 17
ON
Output Frequency
Figure 5.63 Fast Stop Sequence
Figure
5.64.
Drive
Motor switch input
Figure 5.64 Motor Selection
Table 5.37 Parameters for Switching Between Two Motors
Setting 16 Open (Motor 1)
C1-01 to C1-04
C3-01 to C3-04
C4-01
C5-01 to C5-08, C5-12, C5-17, C5-18
E1-, E2-
F1-01 to F1-21
Refer to b4: Delay Timers on page 166
ON
Decelerates at C1-09
PID Block Diagram on page
YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual
ON
ON
TIME
M
Motor 1
M
Motor 2
Setting 16 Closed (Motor 2)
C1-05 to C1-08
C3-21 to C3-24
C4-07
C5-21 to C5-28, C5-32, C5-37, C5-38
E3- to E4-
F1-02 to F1-04, F1-08 to F1-11, F1-14, F1-31 to F1-37
for details.
170.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents