 Alarm Register Contents
The table below shows the alarm codes that can be read out from MEMOBUS/Modbus register 007FH.
Alarm Code
0001H
Undervoltage (Uv)
0002H
Drive Overheat Warning (ov)
0003H
Heatsink Overheat (oH)
0004H
Drive Overheat Warning (oH2)
0005H
Overtorque 1 (oL3)
0006H
Overtorque 2 (oL4)
0007H
Run commands input error (EF)
0008H
Drive Baseblock (bb)
0009H
External Fault 3, input terminal S3 (EF3)
000AH
External Fault 4, input terminal S4 (EF4)
000BH
External Fault 5, input terminal S5 (EF5)
000CH
External Fault 6, input terminal S6 (EF6)
000DH
External Fault 7, input terminal S7 (EF7)
000EH
External Fault 8, input terminal S8 (EF8)
000FH
Internal Fan Fault (FAn)
0010H
Overspeed (oS)
0011H
Speed Deviation (dEv)
0012H
PG Disconnected (PGo)
0014H
MEMOBUS/Modbus Communication Error (CE)
0015H
Option Communication Error (bUS)
0016H
Serial Communication Transmission Error (CALL)
0017H
Motor Overload (oL1)
0018H
Drive Overload (oL2)
001AH
Option Card External Fault (EF0)
001BH
Motor Switch command input during run (rUn)
001DH
Serial Communication Transmission Error (CALL)
001EH
Undertorque Detection 1 (UL3)
001FH
Undertorque Detection 2 (UL4)
0020H
MEMOBUS/Modbus Communication Test Mode Error (SE)
570
Table C.6 Alarm Register 007FH Contents
Fault Name
YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual
Alarm Code
0022H
Motor Overheat (oH3)
0027H
PID Feedback Loss (FbL)
0028H
PID Feedback Loss (FbH)
002AH
Drive Disabled (dnE)
002BH
PG Disconnected (PGo)
0031H
MECHATROLINK Watchdog Timer Error (E5)
0032H
Station Address Setting Error (AEr)
0033H
MECHATROLINK Comm. Cycle Setting Error (CyC)
0034H
High Current Alarm (HCA)
0035H
Cooling Fan Maintenance Time (LT-1)
0036H
Capacitor Maintenance Time (LT-2)
0038H
SI-S EEPROM Error (EEP)
0039H
External Fault (input terminal S1) (EF1)
003AH
External Fault (input terminal S2) (EF2)
003BH
Safe Disable Input (HbbF)
003CH
Safe Disable Input (Hbb)
003DH
Mechanical Weakening Detection 1 (oL5)
003EH
Mechanical Weakening Detection 2 (UL5)
003FH
PLC Alarm (PA1)
0040H
PLC Alarm (PA2)
0041H
Output Voltage Detection Fault (voF)
0042H
IGBT Maintenance Time (90%) (TrPC)
0043H
Soft Charge Bypass Relay Maintenance Time (LT-3)
0044H
IGBT Maintenance Time (50%) (LT-4)
0045H
Braking Transistor Overload (boL)
0048H
Motor Overheat (NTC Input) (oH5)
0049H
DriveWorksEZ Fault (dWAL)
004DH
Thermistor Disconnect (THo)
Fault Name