YASKAWA A1000 Technical Manual page 506

High performance vector control drive type: cimr-a series models: 200 v class: 0.55 to 110 kw, 400 v class: 0.55 to 630 kw
Hide thumbs Also See for A1000:
Table of Contents

Advertisement

B.3 Parameter Table
o2: Digital Operator Keypad Functions
No. (Addr.)
Name
o2-01
LO/RE Key Function Selection
(505H)
o2-02
STOP Key Function Selection
(506H)
o2-03
User Parameter Default Value
(507H)
o2-04
Drive Model Selection
(508H)
o2-05
Frequency Reference Setting
(509H)
Method Selection
o2-06
Operation Selection when Digital
(50AH)
Operator is Disconnected
o2-07
Motor Direction at Power Up when
(527H)
Using Operator
o2-09
Reserved
(50DH)
o2-19
Selection of Parameter Write
(61FH)
During UV
o3: Copy Function
No. (Addr.)
Name
o3-01
Copy Function Selection
(515H)
o3-02
Copy Allowed Selection
(516H)
o4: Maintenance Monitor Settings
No. (Addr.)
Name
o4-01
Cumulative Operation Time
(50BH)
Setting
o4-02
Cumulative Operation Time
(50CH)
Selection
o4-03
Cooling Fan Operation Time
(50EH)
Setting
o4-05
Capacitor Maintenance Setting
(51DH)
506
All Modes
0: Disabled
1: Enabled. LO/RE key switches between LOCAL and REMOTE operation.
All Modes
0: Disabled. STOP key is disabled in REMOTE operation.
1: Enabled. STOP key is always enabled.
All Modes
0: No change.
1: Set defaults. Saves parameter settings as default values for a User Initialization.
2: Clear all. Clears the default settings that have been saved for a User Initialization.
All Modes
Enter the drive model. Setting required only if installing a new control board.
All Modes
0: ENTER key must be pressed to enter a frequency reference.
1: ENTER key is not required. The frequency reference can be adjusted using the up and down
arrow keys only.
All Modes
0: The drive continues operating if the digital operator is disconnected.
1: A fault is triggered (oPr) and the motor coasts to stop.
All Modes
0: Forward
1: Reverse
This parameter requires that drive operation be assigned to the digital operator.
All Modes
Selects if parameter settings can be changed during a DC bus undervoltage condition. To be
used with 24V POWER SUPPLY (PS-A10L, PS-A10H).
0: Disabled
1: Enabled
Note: If the function of o2-19 is enabled, it is possible for a CPF06 Fault to occur. This function
should be used with 24V POWER SUPPLY (PS-A10L, PS-A10H) REVISION B or later.
If the older revision is used, parameter changes might not occur correctly.
All Modes
0: Copy select
1: INV  OP READ (Read parameters from the drive, saving them onto the digital operator.)
2: OP  INV WRITE (Copy parameters from the digital operator, writing them to the drive.)
3: OP  INV VERIFY (Verify parameter settings on the drive to check if they match the data
saved on the operator.)
To read the drive' parameter settings into the digital operator, set o3-02 to 1 (to allow reading).
All Modes
Selects whether the read operation (o3-01 = 1) is enabled or disabled.
0: Read operation prohibited
1: Read operation allowed
All Modes
Sets the value for the cumulative operation time of the drive in units of 10 h.
All Modes
0: Logs power-on time
1: Logs operation time when the drive output is active (output operation time).
All Modes
Sets the value of the fan operation time monitor U4-03 in units of 10 h.
All Modes
Sets the point at which the cumulative timing for the main circuit capacitor maintenance starts.
View monitor U4-05 to determine when the capacitors may require replacement.
YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual
Description
Description
Description
Setting
Page
Default: 1
Min: 0
315
Max: 1
Default: 1
Min: 0
316
Max: 1
Default: 0
Min: 0
316
Max: 2
Default: Determined by
drive capacity
316
Min: –
Max: –
Default: 0
Min: 0
317
Max: 1
Default: 0
Min: 0
317
Max: 1
Default: 0
Min: 0
317
Max: 1
Default: 0
Min: 0
317
Max: 1
Setting
Page
Default: 0
Min: 0
318
Max: 3
Default: 0
Min: 0
318
Max: 1
Setting
Page
Default: 0
Min: 0
318
Max: 9999
Default: 0
Min: 0
318
Max: 1
Default: 0
Min: 0
319
Max: 9999
Default: 0%
Min: 0%
319
Max: 150%