YASKAWA A1000 Technical Manual page 475

High performance vector control drive type: cimr-a series models: 200 v class: 0.55 to 110 kw, 400 v class: 0.55 to 630 kw
Hide thumbs Also See for A1000:
Table of Contents

Advertisement

No.(Addr.)
Name
F1-12
PG 1 Gear Teeth 1
(38BH)
F1-13
PG 1 Gear Teeth 2
(38CH)
F1-14
PG Open-Circuit Detection Time
(38DH)
F1-18
dv3 Detection Selection
(3ADH)
F1-19
dv4 Detection Selection
(3AEH)
F1-20
PG Option Card Disconnect
(3B4H)
Detection 1
F1-21
PG 1 Signal Selection
(3BCH)
F1-30
PG Card Option Port for Motor 2
(3AAH)
Selection
F1-31
PG 2 Pulses Per Revolution
(3B0H)
F1-32
PG 2 Rotation Selection
(3B1H)
F1-33
PG 2 Gear Teeth 1
(3B2H)
F1-34
PG 2 Gear Teeth 2
(3B3H)
F1-35
PG 2 Division Rate for Pulse
(3BEH)
Monitor
F1-36
PG Option Card Disconnect
(3B5H)
Detection 2
F1-37
PG 2 Signal Selection
(3BDH)
F1-50
Encoder Selection
(3D2H)
YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual
V/f
V/f w/PG
OLV/PM
AOLV/PM
Sets the gear ratio between the motor shaft and the encoder (PG).
A gear ratio of 1 will be used if either of these parameters is set to 0.
V/f
V/f w/PG
OLV/PM
AOLV/PM
Sets the time required to trigger a PG Open fault (PGo).
V/f
V/f w/PG
OLV/PM
AOLV/PM
0: Disabled
1: Enabled
V/f
V/f w/PG
OLV/PM
AOLV/PM
0: Disabled
n: Number of pulses that the A and B pulse are reversed that triggers dv4 detection.
V/f
V/f w/PG
OLV/PM
AOLV/PM
0: Disabled
1: Enabled
V/f
V/f w/PG
OLV/PM
AOLV/PM
0: A pulse detection
1: AB pulse detection
V/f
V/f w/PG
OLV/PM
AOLV/PM
Sets the port for the PG option card used by motor 2.
0: CN5-C
1: CN5-B
V/f
V/f w/PG
OLV/PM
AOLV/PM
Sets the number of pulses for a PG option card connected to port CN5-B.
V/f
V/f w/PG
OLV/PM
AOLV/PM
0: Pulse A leads
1: Pulse B leads
V/f
V/f w/PG
OLV/PM
AOLV/PM
Sets the gear ratio between the motor shaft and the encoder (PG).
A gear ratio of 1 will be used if either of these parameters is set to 0.
V/f
V/f w/PG
OLV/PM
AOLV/PM
Sets the division ratio for the pulse monitor used of the PG option card 2 installed to connector
CN5-B. By setting for a three-digit number: xyz, the division ratio becomes = [(1 + x) / yz].
Note: Values 033 to 101 are not available.
V/f
V/f w/PG
OLV/PM
AOLV/PM
0: Disabled
1: Enabled
V/f
V/f w/PG
OLV/PM
AOLV/PM
0: A pulse detection
1: AB pulse detection
V/f
V/f w/PG
OLV/PM
AOLV/PM
Selects the encoder connected the PG-F3 option.
0: EnDat 2.1/01, 2.2/01 Serial Communication + Sin/Cos
1: EnDat 2.2/22 Serial Communication
2: Hiperface
Note: 1. This parameter is not available with models CIMR-A4A0930 and 4A1200.
2. The use of EnDat2.2/22 encoders requires a PG-F3 option with software version 0102
or later. To identify the PG-F3 software version refer to the PG-F3 labeling in the field
designated "C/N" (S + four digit number).
Description
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
B.3 Parameter Table
Setting
Page
Default: 0
Min: 0
226
Max: 1000
Default: 0
Min: 0
226
Max: 1000
Default: 2.0 s
Min: 0.0 s
225
Max: 10.0 s
Default: 10
Min: 0
227
Max: 10
Default: 128
Min: 0
227
Max: 5000
Default: 1
Min: 0
227
Max: 1
Default: 0
Min: 0
227
Max: 1
Default: 1
Min: 0
227
Max: 1
Default: 1024 ppr
Min: 1 ppr
225
Max: 60000 ppr
Default: 0
Min: 0
226
Max: 1
Default: 0
Min: 0
226
Max: 1000
Default: 0
Min: 0
226
Max: 1000
Default: 001
Min: 001
226
Max: 132
Default: 1
Min: 0
227
Max: 1
Default: 0
Min: 0
227
Max: 1
Default: 0
Min: 0
228
Max: 2
475
B

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents