B.3 Parameter Table

 A: Initialization Parameters
The A parameter group creates the operating environment for the drive. This includes the parameter Access Level, Motor
Control Method, Password, User Parameters and more.
A1: Initialization Parameters
No.(Addr.)
Name
A1-00
(100H)
Language Selection
<3>
A1-01
(101H)
Access Level Selection
<2>
A1-02
(102H)
Control Method Selection
<3>
A1-03
Initialize Parameters
(103H)
A1-04
Password
(104H)
A1-05
Password Setting
(105H)
A1-06
Application Preset
(127H)
A1-07
DriveWorksEZ Function Selection 0: DWEZ disabled
(128H)
<2> Default setting value is dependent on the Application Preset selected with parameter A1-06.
<3> The parameter setting is not reset to the default value when A1-03 is used to initialize the drive.
YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual
All Modes
0: English
1: Japanese
2: German
3: French
4: Italian
5: Spanish
6: Portuguese
7: Chinese
8: Czech
9: Russian
10: Turkish
11: Polish
12: Greek
Note: 1. Settings 8 to 12 can be selected from an LCD operator with version (REV) F or later.
The version is listed on the back of the LCD operator.
2. The setting range is 0 to 7 in models CIMR-A4A0930 and 4A1200.
All Modes
0: View and set A1-01 and A1-04. U- parameters can also be viewed.
1: User Parameters (access to a set of parameters selected by the user, A2-01 to A2-32)
2: Advanced Access (access to view and set all parameters)
All Modes
0: V/f Control
1: V/f Control with PG
2: Open Loop Vector Control
3: Closed Loop Vector Control
5: Open Loop Vector Control for PM
6: Advanced Open Loop Vector Control for PM
7: Closed Loop Vector Control for PM
All Modes
0: No initialization
1110: User Initialize (parameter values must be stored using parameter o2-03)
2220: 2-wire initialization
3330: 3-wire initialization
5550: oPE04 error reset
All Modes
When the value set into A1-04 does not match the value set into A1-05, parameters A1-01
through A1-03, A1-06, A1-07, and A2-01 through A2-32 cannot be changed.
All Modes
0: General-purpose
1: Water supply pump
2: Conveyor
3: Exhaust fan
4: HVAC fan
5: Air compressor
6: Elevator
7: Hoist
All Modes
1: DWEZ enabled
2: Digital input (enabled when H1- = 9F)
Description
B.3 Parameter Table
Setting
Page
Default: 0
Min: 0
142
Max: 12
Default: 2
Min: 0
142
Max: 2
Default: 0
Min: 0
143
Max: 7
Default: 0
Min: 0
143
Max: 5550
Default: 0000
Min: 0000
144
Max: 9999
Default: 0
Min: 0
146
Max: 7
Default: 0 
Min: 0
147
Max: 2
453