5.5 E: Motor Parameters
V/f Pattern Settings E1-04 to E1-13
Set E1-03  E to monitor, but not change, the V/f pattern using parameters E1-04 to E1-13. To create a new V/f pattern,
set E1-03 to F. Refer to
Figure 5.56
Note: Certain E1- parameters might not be visible depending on the selected control mode.
for details.
No.
E1-04
E1-05
E1-06
E1-07
E1-08
E1-09
E1-10
E1-11
<5>
E1-12
<5>
E1-13
<1> Default setting is determined by E5-01 in OLV/PM. The setting range is 0.0 to 400.0 Hz when E5-01 = FFFF.
<2> Default setting is determined by the Drive Model, Control Method, and Drive Duty.
<3> When using PM motors, the default setting is determined by the motor code set to E5-01.
<4> Values shown here are for 200 V class drives. Double values when using a 400 V class unit.
<5> Parameter ignored when E1-11 and E1-12 are set to 0.0.
<6> When Auto-Tuning is performed, E1-13 and E1-05 will be set to the same value.
Figure 5.56
Note: 1. The following condition must be true when setting up the V/f pattern: E1-09  E1-07  E1-06  E1-11  E1-04
2. To make the V/f pattern a straight line below E1-06, set E1-09 = E1-07. In this case the E1-08 setting is disregarded.
3. E1-03 is unaffected when the parameters are initialized using parameter A1-03, but the settings for E1-04 through E1-13 are returned
to their default values.
4. Parameters E1-11, E1-12, and E1-13 should only be used to fine-tune the V/f pattern in the constant output range. These parameters
rarely need to be changed.
 E2: Motor 1 Parameters
These parameters contain the motor data needed for motor 1. They are set automatically when Auto-Tuning is performed
(this includes Rotational Auto-Tuning, Stationary Auto-Tuning 1 and 2). If Auto-Tuning cannot be performed, refer to
Auto-Tuning Fault Detection on page 360
Note: As the motor parameters for a PM motor are set up in the E5- parameters, parameters for induction motors (E2-) are
hidden when a PM motor control mode is selected for motor 1 (i.e., parameter A1-02 is set to 5, 6, or 7).
E2-01: Motor Rated Current
Provides motor control, protects the motor, and calculates torque limits. Set E2-01 to the full load amps (FLA) stamped
on the motor nameplate. If Auto-Tuning completes successfully, the value entered to T1-04 will automatically be saved
to E2-01.
No.
E2-01
Note: 1. Display is in the following units. 
 CIMR-A2A0004 to 2A0040, CIMR-A4A0002 to 4A0023: 0.01 A units
 CIMR-A2A0056 to 2A0312, CIMR-A4A0031 to 4A0675: 0.1 A units
 CIMR-A4A0930 to 4A1200: 1 A units
2. An oPE02 error will occur if E2-01  E2-03. Set E2-03 correctly to prevent this error.
216
for an example custom V/f pattern.
Parameter Name
Maximum Output Frequency
Maximum Voltage
Base Frequency
Middle Output Frequency
Middle Output Frequency Voltage
Minimum Output Frequency
Minimum Output Frequency Voltage
Middle Output Frequency 2
Middle Output Frequency Voltage 2
Base Voltage
Output Voltage (V)
Figure 5.56 V/f Pattern
for detail.
Parameter Name
Motor Rated Current
YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual
Refer to Parameter Table on page 453
40.0 to 400.0 Hz
0.0 to 255.0 V
Frequency (Hz)
10% to 200% of the drive rated current.
Setting Range
<1>
0.0 to 255.0 V
<4>
0.0 to [E1-04]
<1>
0.0 to [E1-04]
0.0 to 255.0 V
<4>
0.0 to [E1-04]
<1>
0.0 to 255.0 V
<4>
0.0 to [E1-04]
0.0 to 255.0 V
<4>
<4>
Setting Range
Determined by
C6-01 and o2-04
Default
<2> <3>
<2> <3>
<2> <3>
<2>
<2>
<2> <3>
<2>
0.0 Hz
0.0 V
0.0 V
<6>
Default