b4-01, b4-02: Timer Function On-Delay, Off-Delay Time
b4-01 sets the on-delay time for switching the timer output. b4-02 sets the off-delay time for switching the timer output.
No.
b4-01
b4-02
Timer Function Operation
When the timer function input closes for longer than the value set in b4-01, the timer output switches on. When the timer
function input is open for longer than the value set in b4-02, the timer output function switches off.
demonstrates the timer function operation.
Figure 5.24
Multi-function Contact
Input: Timer Function (H1-
Multi-function Contact
Output: Timer Function (H2-
b4-03 to b4-08: H2- ON-Delay and OFF-Delay Time
Sets the length of the delay time for contact outputs to open or close for the related functions set in H2-.
Note: This parameter is not available in models CIMR-A4A0930 and 4A1200.
No.
b4-03
b4-04
b4-05
b4-06
b4-07
b4-08
Internal data of H2-01
Multi-Function Digital
Outputs of H2-01
Note: Even if the length of the off-delay time and on-delay time for multi-function digital output are each less than 100 ms,
the multi-function digital output closes for at least 100 ms.
 b5: PID Control
The drive has a built in PID (Proportional + Integral + Derivative) controller that can be used for closed loop control of
system variables such as pressure, temperature, and so on. The difference between the target and the feedback value
(deviation) is fed into the PID controller. The PID controller adjusts the drive output frequency in order to minimize the
deviation, providing accurate control of system variables.
P Control
The output of P control is the product of the deviation and the P gain so that it follows the deviation directly and linearly.
With P control, only an offset between the target and feedback remains.
YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual
Name
Timer Function On-Delay Time
Timer Function Off-Delay Time
ON
= 18)
ON
= 12)
b4-01
b4-02
Figure 5.24 Timer Operation
Name
H2-01 ON Delay Time
H2-01 OFF Delay Time
H2-02 ON Delay Time
H2-02 OFF Delay Time
H2-03 ON Delay Time
H2-03 OFF Delay Time
ON
ON
b4-04
b4-03
Time period that the multi-function
digital output is closed ≥ 100 ms
Setting Range
0.0 to 3000.0 s
0.0 to 3000.0 s
ON
ON
b4-01
b4-02
Setting Range
0 to 65536 ms
0 to 65536 ms
0 to 65536 ms
0 to 65536 ms
0 to 65536 ms
0 to 65536 ms
ON
ON
b4-03
b4-04
Time period that the multi-function
digital output is closed < 100 ms
Time period that the multi-function
digital output is closed = 100 ms
5.2 b: Application
Default
0.0 s
0.0 s
Figure 5.24
On (Closed)
Off (Open)
On (Closed)
Off (Open)
Default
0 ms
0 ms
0 ms
0 ms
0 ms
0 ms
On (Closed)
Off (Open)
On (Closed)
Off (Open)
5
167