Periodic Maintenance

The drive has Maintenance Monitors that keep track of component wear. This feature provides advance maintenance
warning and eliminates the need to shut down the entire system for unexpected problems. The drive allows the user to
check predicted maintenance periods for the components listed below.
For replacement parts, contact the distributor where the drive was purchased or contact YASKAWA directly.
• Cooling Fan, Circulation Fan, Control Board Cooling Fan
• Electrolytic Capacitors
• Inrush Prevention Circuit
• IGBTs
 Replacement Parts
Table 7.3
contains the estimated performance life of components that require replacement during the life of the drive.
Only use YASKAWA replacement parts for the appropriate drive model and revision.
Component
Cooling Fan, Circulation Fan, Control Board Cooling Fan
Electrolytic Capacitors
<1> The drive has few serviceable parts and may require complete drive replacement.
NOTICE: Estimated performance life based on specific usage conditions. These conditions are provided for the purpose of replacing
parts to maintain performance. Some parts may require more frequent replacement due to poor environments or rigorous use. Usage
conditions for estimated performance life:
• Ambient temperature: Yearly average of 40°C (IP20/IP00 enclosure)
Yearly average of 30°C (IP20/NEMA 1, UL Type 1 enclosure, side-by-side mounting, finless drive or external heatsink installation)
• Load factor: 80% maximum
• Operation time: 24 hours a day
Performance Life Monitors Maintenance Monitors
The drive calculates the maintenance period for components that may require replacement during the life of the drive. A
percentage of the maintenance period is displayed on the digital operator by viewing the appropriate monitor parameter.
When the maintenance period reaches 100%, there is increased risk that the drive may malfunction. YASKAWA
recommends checking the maintenance period regularly to ensure maximum performance life.
Set parameters L8-12 (Ambient Temperature Setting) and L8-35 (Installation Method Selection) for use with the
installation environment when using maintenance monitors.
Refer to Recommended Periodic Inspection on page 379
Table 7.4 Performance Life Monitors Used for Component Replacement
Parameter
Component
Cooling Fan, Circulation Fan, 
U4-03
Control Board Cooling Fan
U4-04
U4-05
DC Bus Capacitors
U4-06
Inrush (pre-charge) Relay
U4-07
IGBT
YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual
Table 7.3 Estimated Performance Life
Displays the accumulated operation time of the fan, from 0 to 99999 hours. This value is automatically reset to 0 once it
reaches 99999.
Displays the accumulated fan operation time as a percentage of the specified maintenance period.
Displays the accumulated time the capacitors are used as a percentage of the specified maintenance period.
Displays the number of times the drive is powered up as a percentage of the performance life of the inrush circuit.
Displays the percentage of the maintenance period reached by the IGBTs.
Estimated Performance Life
10 years
for more details.
Contents
7.3 Periodic Maintenance
10 years
<1>
7
381