The optional PC Configuration Software cannot be used while a test mode is active.
All events generated while the system is in test mode will be logged in the event history. Therefore a record
of the testing can be generated once it is complete (see Normal Operation, Generate Reports).

8.1.2 Field Inputs Test

Note: Engineer access level is required.
During this test, all field device inputs will be displayed by the Touchpoint Pro system, but the Cause and
Effect matrix will not be evaluated. No outputs will be generated.
The purpose of this test is to check that the input field devices are connected to the correct input channel of
the Touchpoint Pro system. Typically, this can be done either by applying gas to the sensor in the field or by
forcing the mA output of the sensor to a given value. The gas concentration and alarm states raised for the
channel can be viewed on the touchscreen or the Web Server.
To use the Field Inputs Test mode:
1. If not already logged in, login with a valid engineer level user name
2. From the System Status screen select the Extras icon then Diagnostics
3. Press the Menu icon
4. The system will ask you to confirm, press Yes to proceed
5. The system will display a confirmation message, click on OK and you will be automatically navigated
to the Active Events screen
6. Proceed with the test of the field devices. To see more detailed information at any time, select the
channel of interest and select Input Details from the popup menu
Note: If the test is done from the Active Events screen, the channel of interest will be shown as soon as
its state changes, e.g. a threshold alarm is generated. Alternatively, you may wish to work from the Inputs
screen (return to System Status screen and select Inputs ) by scrolling down to the channel of interest
7. When the test is complete, return to the System Status screen and select the Extras icon then
Diagnostics
8. Press the Menu icon
9. The system will show a confirmation message that it has returned to normal operation
Ensure that the system is returned to normal operation once testing is complete.