Honeywell touchpoint Pro Operating Instructions Manual page 142

Hide thumbs Also See for touchpoint Pro:
Table of Contents

Advertisement

MAN0923_Issue 3_04/15
Error
Message
Code
104
Operation failed; response result
failure
105
Operation failed; response timeout
106
Operation failed; CRC error
107
Operation failed; session expired
108
CCB-COB communication failed.
109
Operation failed; CCB is not
responding.
110
Channel cannot be commissioned;
no free Channel ID available. Please
de-commission an adequate channel
and try again!
111
Operation failed; invalid command
code received from CCB.
112
Module cannot be commissioned.
You have exceeded the maximum
number of 48 I/O modules. Use the
Remove Module or Replace Module
function in the System Configuration.
113
Not used
114
Restore operation failed - backup file
could not be found
115
Operation cannot be performed -
please insert SD Card!
116
Operation failed; transaction could
not be closed
117
Operation failed; response parsing
failure
9. Problem Solving
Possible Cause
Internal communication
error
Please refer to error 104 Please refer to error 104
Please refer to error 104 Please refer to error 104
A user login will time
out after 20 minutes of
inactivity
Please refer to error 2
Please refer to error 2
Touchpoint Pro has a
maximum capacity of
64 input and 128 output
channels
Please refer to error 2
Touchpoint Pro has a
maximum capacity of
16 Input and 32 Output
Modules
An error occurred during
configuration restore
Please refer to error 2
Please refer to error 2
142
Remedial Action
1. Please retry the operation.
2. If still unsuccessful, on the front panel, press the
Accept and Reset buttons together for 10 s, which
will restart the COB.
3. If the error has not cleared, if possible cycle the
power to the system.
4. If the problem persists, please contact your local
service representative.
The system will automatically request a new login
Please refer to error 2
Please refer to error 2
If more channels than 64 inputs and 128 outputs
are required an additional Touchpoint Pro system is
needed. Contact your local representative to discuss
your requirements.
Please refer to error 2
If more channels than 64 inputs and 128 outputs
are required an additional Touchpoint Pro system is
needed. Contact your local representative to discuss
your requirements.
1. Check that the correct file is being used for the
restore operation, and is saved as \Hard Disk\
Touchpoint Pro Configuration\Touchpoint
ProConfig.bin
2. Retry the operation.
3. On the front panel, press the Accept and Reset
buttons together for 10 s, which will restart the COB.
4. Retry the operation.
1. Check that the SD Card memory device has
enough free memory available for the operation.
2. Check that it is correctly inserted in the socket.
3. Retry the operation.
Please refer to error 2
Please refer to error 2
Touchpoint Pro
Operating Instructions

Advertisement

Table of Contents
loading