Analogue Input Module Mv Bridge - Honeywell touchpoint Pro Operating Instructions Manual

Hide thumbs Also See for touchpoint Pro:
Table of Contents

Advertisement

MAN0923_Issue 3_04/15
10.6.2 Analogue Input Module mA
Description
Sensor Configuration
Signal Measurement Range
Supply Voltage
Field Device Supply Voltage
Single Channel Field Device
Supply current
Total Field Device supply current
Power Consumption
Power Dissipation
Sense Resistance
Connector Coding

10.6.3 Analogue Input Module mV Bridge

Description
Electrical Connection
Supply Voltage
Sensor Drive method
Programmable Current Range
Maximum Loop Resistance
Input Range
Power Consumption
Power Dissipation
Connector Coding
10. Specifications
4-channel 4 – 20 mA Analogue Input Module with two or three-wire interface to detector
4 x two-wire or three-wire (current sourced from detector)
0 – 25 mA
18 – 32 VDC (Supplied from Self Enclosed Low Voltage source only)
Supply Voltage (Vs) – 0.7 V
Maximum 1 A
Total Maximum current : 2 A at 70 °C ambient
Total Maximum current : 4 A at 60 °C ambient
0.8 W (Excluding sensor supply)
Maximum 3.7 W, at 4 A total field device load
Maximum 2.1 W, at 2 A total field device load
101 Ω
Analogue Input Module connectors (TB1–TB4) have coding keys to avoid incorrect wiring
4-channel Analogue Input Module for Catalytic Bridge sensors
4 x three-wire mV Bridge
18 – 32 VDC (Supplied from Self Enclosed Low Voltage source only)
Constant current
180 – 360 mA
Total Maximum loop resistance: 40 Ω at 200 mA (including Sensor)
Total Maximum loop resistance: 27 Ω at 360 mA (including Sensor)
±15 mV to ±600 mV
Maximum 1.2 W (Excluding Sensors)
Maximum 3.5 W
Analogue Input Module connectors (TB1–TB4) have coding keys to avoid incorrect wiring
153
Touchpoint Pro
Operating Instructions

Advertisement

Table of Contents
loading

Table of Contents