2. Overview / Introduction

2.6.1 Available Modules

Analogue Input Module 4–20 mA (AIM mA)
Analogue Input Module mV Bridge (AIM mV)
Digital Input Module (DIM)
Relay Output Module (ROM)
Note: Communication/Power Rails may be included in the system without any I/O Modules, however there is
a limit of 5 such Communication/Power Rails within the full 3 km loop of the system.
2.7 System Interaction
The User Interface consists of:
Interface software with three ways to access:
Touchscreen for normal system operation, maintenance and configuration
Web Server for remote access to view normal system operation
PC Configuration Software (optional) for convenient system configuration
Accept and reset buttons on the front panel of the Touchpoint Pro Controller
Power, Alarm, Fault and Inhibit LEDs on the front panel of the Touchpoint Pro Controller
Buzzer on the Touchpoint Pro Controller
Further System Interfaces consist of:
Two master relays, System Failure and System Fault
Connections for SD Card and USB memory device
10/100 Mbps Ethernet connection
Optional digital bus interface
4-channel Analogue Input Module for 2 or 3 wire 4-20mA detector
signals
4-channel Analogue Input Module for mV-Bridge signals; powers up to 4
catalytic flammable gas detectors
4-channel Digital Input Module for switched input devices such as
manually operated push buttons. Can also be used for remote alarm
acknowledge, reset and output inhibit
4-channel Relay Output Module incorporating 4 SPCO relays; suitable to
activate field mounted annunciators
23