8.1.3 Configuration Settings Test

Note: Engineer access level is required
During this test, all field device inputs will be ignored by the Touchpoint Pro system. The Cause and Effect
matrix will not be evaluated. No outputs will be generated.
The purpose of this test is to check that input channels are configured correctly, including alarm, warning,
fault thresholds etc. The gas concentration and alarm states raised for the channel as a consequence of
forcing the input to a given value can be viewed on the touchscreen or the Web Server.
To use the Configuration Settings Test mode:
1. If not already logged in, login with a valid engineer level user name
2. From the System Status screen select the Extras icon then Diagnostics
3. Press the Menu icon
4. The system will ask you to confirm, press Yes to proceed
5. The system will display a confirmation message, click on OK and you will be automatically navigated
to the Inputs screen
6. Select the channel to be tested and select Input Details from the popup menu
7. From the Input Details screen, press the Menu icon
8. Enter the gas concentration that you want to simulate. This can include over and under range values
9. The system will return to the Input Details screen, where it will show the simulated gas value as well as
any corresponding active events (e.g. Alarm 1)
10. When ready, press the Menu icon
11. Repeat steps 7-10 as required to complete the channel test
12. Return to the Inputs screen and repeat steps 6-10 for the next channel
13. When the test is complete, return to the System Status screen and select the Extras icon then
Diagnostics
14. Press the Menu icon
15. The system will show a confirmation message that it has returned to normal operation
Ensure that the system is returned to normal operation once testing is complete.
8. Maintenance
and select Configuration Settings Test
and select Clear Force
and select Stop Configuration Settings Test
WARNING
112
and select Force Value
Touchpoint Pro
Operating Instructions