Honeywell touchpoint Pro Operating Instructions Manual page 68

Hide thumbs Also See for touchpoint Pro:
Table of Contents

Advertisement

MAN0923_Issue 3_04/15
5.1 General
System interfaces consist of:
Interface software with three ways to access
Touchscreen for normal system operation, maintenance and configuration
Licensed Web Server for remote access to view normal system operation
Licensed PC Configuration Software (optional) for convenient system configuration
Accept and reset buttons on the front panel of the Touchpoint Pro Controller
Power, Alarm, Fault and Inhibit LEDs on the front panel of the Touchpoint Pro Controller
Buzzer on the Touchpoint Pro Controller
Further Interfaces consist of:
Two master relays, System Failure and System Fault
Connections for SD Card and USB memory device
10/100 Mbps Ethernet connection
Optional digital bus interface
The interface software has two distinct modes of operation – Configuration Mode and Visualisation Mode,
Within each mode, access to certain functions is restricted by the use of password protected access
levels. There are four hierarchical access levels - View is available to all users while Operator, Maintenance
Engineer and Administrator are password protected. Each user can be assigned one access level.
Access to certain functions is also restricted via the Web Server for safety reasons.
5.2 Access Levels
The table below details the access levels for the User Interface. The highest level of password protected
access is Administrator, then Maintenance Engineer, then Operator. Broadly speaking, the Administrator
can commission modules and configure channels, the Maintenance Engineer can edit channel configuration
and do calibration, and the Operator can interact with the system during normal day-to-day operation such
as acknowledging and resetting events. The table also shows which functions are not available via the Web
Server for safety reasons (for example, Calibration).
Touchpoint Pro is supplied with a default Administrator level account. For security reasons this will be
attached to the system touchscreen. When the system is configured, at least one new Administrator
account should be created. The default Administrator should then log out and then log back in as the new
Administrator, and should then delete the default Administrator account to prevent unauthorized access.
The Administrator can create other users with Administrator level access or lower and the Maintenance