MAN0923_Issue 3_04/15
16. Appendix 3 - Wiring Diagrams

16.10 ROM With External Auxiliary Supply in NC and NO Configuration

+V
External Supply
GND
Notes:
1. For all shielded cables, shield (screen) should be connected to Earth tag bar/bus bar provided in Touchpoint Pro enclosure.
2. Maximum +24Vdc Output Load, 1.5A per channel, and 1.5A total per module. With Overload protection.
3. Maximum Relay contact rating, 5A@ 24Vdc and 5A@230Vac (resistive loads only)
Recommended Cable:
2 Core, Twisted, Mesh Type
Shielded, 1.5mm
2
or 2.5mm
2
R
LOAD
E
R
LOAD
R
LOAD
R
LOAD
220
Operating Instructions
ROM Module
+24VDC
+V
14
-V
0VDC
15
NO
1
NC
2
C
3
+24VDC
+V
17
-V
0VDC
18
NO
4
NC
5
C
6
+24VDC
+V
20
-V
0VDC
21
NO
7
NC
8
C
9
+24VDC
+V
23
-V
0VDC
24
NO
10
NC
11
C
12
Touchpoint Pro
Channel 1
(NC Configuration)
Channel 2
(NC Configuration)
Channel 3
(NO Configuration)
Channel 4
(NO Configuration)