MAN0923_Issue 3_04/15
Ne pas déconnecter les terminaux ou supprimer les modules lorsque l'appareil est
This wall mounted enclosure is certified for use in hazardous areas / locations (Class 1 Div.2, Class 1
Zone 2, and Zone 2 [ATEX]). This enclosure can only be used as a remote unit due to its classification,
and no User Interface option is available.
This unit is IP 66 Type 4 & 4X, Class 1 (grounded), and can be installed indoors or outdoors in a Pollution
Degree 4 environment, and can be exposed to rain, snow and direct sunlight.
The upper T
a
may be reduced dependent on internal power dissipation. See Rating Plate for details.
Part Number
Material
Dimensions (H x W x D)
Weight
Operating Conditions
Power Supplies
Pmax

10.3 Floor Standing Enclosures

Ventilated enclosures are IP20, Type 1, Class 1 (grounded), installation category 2, and must only be
installed in a place that provides a Pollution Degree 2 environment. I.e. places that afford protection from
rain, snow and direct sunlight. Such an environment would include laboratories, offices and Control rooms.
Non-ventilated (sealed) enclosures are IP56, Type 4 & 12, Class 1 (grounded), installation category 2, and
can be installed indoors or outdoors in a Pollution Degree 3 environment that affords total protection from
rain, snow and direct sunlight.
The upper T
a
may be reduced dependent on internal power dissipation. See Rating Plates for details.
10. Specifications
Do not disconnect terminals or remove modules when energised.
(Class 1 Div.2, Class 1 Zone 2, and Zone 2 [ATEX])
AVERTISSEMENT
(Classe 1 Div.2, Classe 1 Zone 2, et Zone 2 [ATEX])
TPPR-V-1241
Stainless Steel
780 x 510 x 300 mm
42 Kg (Basic Unit)
-40 to +65 °C (T
), 0 – 100 %RH (condensing)
a
24 VDC Nominal (18 – 32 VDC), 0 – 20 A max.
See Rating Plate
Protect from direct exposure to precipitation and sunlight.
AVERTISSEMENT
Protéger des expositions directes au soleil et de la pluie.
WARNING
sous tension.
WARNING