14.6.3 Command Poll Registers

Command Poll
Block Active
Block
1
41001
2
41101
3
41201
4
41301
5
41401
6
41501
7
41601
8
41701
9
41801
10
41901
Allowed values for the Result register 41n05 (n = 0 to 9)
Value
Meaning
0
Success
1
Command not permitted
2
Inter process communication failure
67
Failure
14.6.4 Command Types Available
Note: Function 06 cannot be used for SIL channels
Command Type Description
23
Alarm Acknowledge
24
Alarm Reset
25
Set Inhibit
26
Clear inhibit
Example: Alarm Acknowledge (Command Type)
Register
Block Active
(41n01)
Value
1
Channel Type
Channel ID
41002
41003
41102
41103
41202
41203
41302
41303
41402
41403
41502
41503
41602
41603
41702
41703
41802
41803
41902
41903
Channel Type
Channel ID
(41n02)
(41n03)
105
2
190
Command Type Command Data Result
41004
41005
41104
41105
41204
41205
41304
41305
41404
41405
41504
41505
41604
41605
41704
41705
41804
41805
41904
41905
Command Type
Command Data
(41n04)
(41n05)
23
0
Touchpoint Pro
Operating Instructions
41006
41106
41206
41306
41406
41506
41606
41706
41806
41906
Result (41n06)
(Updated upon request
execution)