Appendix 2 - Configurable Parameter Reference Guide - Honeywell touchpoint Pro Operating Instructions Manual

Hide thumbs Also See for touchpoint Pro:
Table of Contents

Advertisement

MAN0923_Issue 3_04/15
15. Appendix 2 - Configurable
Parameter Reference Guide
Note: For text fields, the maximum number of characters that can be entered is given throughout this
reference guide. However, in exceptional cases where many wide characters are used the text may be too
long for the field. The full text will be visible in any reports.
15.1 Analogue Input Module 4-20 mA
The Analogue Input Module 4-20 mA has the option to use the sensor catalogue (basic / extended),
configure a custom channel, or copy from a configured channel (basic / extended).
Note: When making changes using Extended options, it is the user's responsibility to determine whether
other settings have been affected and to make any corresponding changes.
If a basic configuration is selected, only the first two screens detailed below will be used (Commission
Channel and Field Device Selection). The rest of the configuration will be programmed automatically, either
from the sensor catalogue or from the channel that is being copied.
Note: If a channel is configured from the sensor catalogue, it is possible to edit individual settings afterwards
(see Section "Editing a Configured Channel").
15.1.1 Commission Channel
Access Level: Administrator
Parameter Name
Default Setting
Channel ID
Next available
Channel Location
"Channel <Channel ID>" Maximum 30
Tag
Channel Custom ID
"Channel <Channel ID>" Maximum 20
Note: Channel Location Tag and Channel Custom ID only require Engineer level access for editing
15.1.2 Field Device Selection
Access Level: Administrator
Parameter Name Default Setting
Field Device Name "Generic Field Device"
Sensor Name
"Generic Sensor"
Value Range
1 to 64
Alphanumeric Characters
Alphanumeric Characters
Value Range
Maximum 30 Alphanumeric
Characters
Maximum 30 Alphanumeric
Characters
192
Comment
Can only be assigned during first time configuration.
Otherwise de-commission the channel and re-assign
another channel number
30 character location tag name. This is the main
channel description used throughout the interface
20 character custom ID. This is displayed on the
"Channel Details" screen and in the Configuration
Report
Comment
If the sensor catalogue is used, a list of available field
devices will be displayed for selection.
If copy channel is being used, this value cannot be
changed
If the sensor catalogue is used, a list of available
gases and ranges will be displayed for selection.
If copy channel is being used, this value cannot be
changed
Touchpoint Pro
Operating Instructions

Advertisement

Table of Contents
loading

Table of Contents