15. Appendix 2 - Configurable
Parameter Reference Guide

15.1.3 Sensor Settings

Access Level: Administrator
Parameter Name Default Setting
Gas Name
"Gas"
Gas Unit
"%FSD"
15.1.4 Range Settings
Access Level: Administrator
Parameter Name
Default Setting
Signal Range Min
4 mA
Signal Range Max
20 mA
Gas Range Min
0
Gas Range Max
100
15.1.5 Display Settings
Access Level: Administrator
Parameter Name
Default Setting
Peak Hold Enable
Disabled
Note: The number of decimal places to be displayed is determined by the Gas Range Max setting as follows:
This is also the resolution at which data will be logged for the trend report.
Value Range
Maximum 10 Alphanumeric Characters
%FSD, %LEL, % Vol., ppm, ppb, mA, mV, mg/
m3, LEL.m or maximum 5 Alphanumeric
Characters
Value Range
0.5 mA to 4 mA
12 mA to 24 mA
Sensor / Unit specific
Sensor / Unit specific
Value Range
Enabled / Disabled
Gas Range Max
≥ 100
≥ 10 and < 99
< 10
Comment
FSD – Full Scale Deflection
LEL – Lower Explosive Limit
LEL.m – LEL metres
Comment
X1 = Signal Range Min (Electrical Input from Sensor)
X2 = Signal Range Max (Electrical input from Sensor)
Y1 = Gas Range Min
Y2 = Gas Range Max
Gas concentration (y) is calculated as follows:
y = (((Y2-Y1)/(X2-X1))*(x-X1))+Y1
Comment
If "Peak Hold" is enabled, and the gas reading rises above
the configured full scale value, the channel will display the
maximum gas reading that has been measured until it is reset
Decimal Places
0
1
2
193