10.1.3 19" 5U Remote Unit Enclosure without User Interface

Part Number
Material
Earthing Points
Dimensions (H x W x D)
Weight
10.2 Wall Mounted Enclosures
All wall mounted enclosures are Equipment Class 1 (grounded) and Installation Category 2, and have
additional restrictions as shown under each sub- heading below.
Protect the User Interface from direct exposure to precipitation and sunlight.
Protéger l'interface utilisateur des expositions directes au soleil et de la pluie.
10.2.1 Wall Mount Controller Enclosures with User Interface
These units are IP 66, Type 4 & 12, Class 1 (grounded), and can be installed indoors or outdoors in a
Pollution Degree 3 environment that affords total protection from rain, snow and direct sunlight.
a
The upper T
may be reduced dependent on internal power dissipation. See Rating Plates for details.
Part Number
Material
Dimensions (H x W x D)
Weight
Operating Conditions
Power Supplies
Pmax
10. Specifications
TPPR-V-0612
Mild Steel
M8 (main grounding) other M6
483 x 222 x 110 mm
6 Kg
WARNING
AVERTISSEMENT
TPPR-V-1210
Mild Steel
600 x 600 x 300 mm
37 Kg
-20 to +55 °C (T
24 VDC Nominal (18 – 32 VDC), 0 – 80 A max.
145
TPPR-V-1220
Mild Steel
800 x 600 x 300 mm
46 Kg
), 0 – 100 %RH (condensing)
a
100 – 240 VAC, 50/60 Hz, 0 – 20 A max.
See Rating Plate
Touchpoint Pro
Operating Instructions
TPPR-V-1230
Mild Steel
1200 x 800 x 300 mm
81 Kg