10.4.5 Power Supply Redundancy Module (RDN Module)

Description
Input Voltage Range
Number of Inputs
Input Current (max.)
Output Reverse Voltage (max.)
Output Current (max.)
Output Voltage Drop
Dimensions
Storage Conditions
Operating Conditions
10.4.6 Uninterruptible Power Supply Module (UPS)
Description
Input Current
Output Voltage
Output Current
Allowed Batteries
Dimension
Operating Conditions
Operating Humidity
De–rating 60 °C to 70 °C
Storage Conditions
10. Specifications
Suitable for redundant operation of DC 24 V
8.4 – 36.4 VDC
2
20 A per input
40 VDC
40 A
72 mV typical for input: 2 x 10 A, 140 mV typical for input: 2 x 20 A
36 mm x 124 mm x 127 mm (W x H x D)
–40 °C to +70 °C
–40 °C to +85°C, 5 to 95 %RH
23.3 VDC – 30 VDC
70 mA typical internal current consumption
Current consumption for battery charging in constant current mode at 24V input
1.7 A typical at battery selector position <10Ah
3.4 A typical at battery selector position >10Ah
DC 24 V (nominal) in Normal Operation
Adjustable in Battery Operation
Max. 25 A in Normal Operations min. 20 A in Battery Operation
2 x 12 V
3.9 Ah – 130 Ah
VRLA (sealed lead acid) type
46 mm x 124 mm x 127 mm (W x H x D)
–40 °C to +70 °C, 5 to 95 %RH (non–condensing)
5 to 95 %RH (non–condensing)
0.5 A / ºC
–40 °C to +85 °C, 5 to 95 %RH (non-condensing)