6.1 Introduction
This chapter explains several operations that may be required during commissioning. Users should
complete the First Time Switch On, Set Date Time and Language, Program Users and Passwords, and
if required Setup Web Server. If the PC Configuration Software is being used, complete First Time Switch
On and Set Date, Time and Language, then Setup PC Configuration Software using the touchscreen,
then continue through the procedures using the PC Configuration Software.
If the system was ordered from Honeywell Analytics with default channel configurations, complete the
section Verify Configuration and Program Tags for the Analogue Input channels, before proceeding with
Channel Configuration for the Digital Input and Relay Output channels.
First Time Switch On
Set Date, Time and Language
Program Users and Passwords
Setup Web Server
Setup PC Configuration Software
Verify Default Configuration and Program Tags
Module Configuration
Channel Configuration
6.2 First Time Switch On
1. Before applying power to the unit, ensure that the wiring to the unit is correct and all electrical
connections are in accordance with Section 4
2. Apply power. Check that the DC supply voltage is between 18 and 32 Vdc. This can be conveniently
checked for example at the Vaux terminals of a Relay Output Module (preferably furthest from the
power source) or at the V+ and V- terminals of an Analogue Input Module
3. The system start up sequence lasts for 3 - 10 minutes depending on the size of the system
4. When start up is completed, Touchpoint Pro will display the System Status screen, indicating the
current status of the system
Note: If Analogue Input mV Bridge channels have been configured but not calibrated, the channels will be in
Inhibit, which will be indicated on the System Status screen.
The Touchpoint Pro Controller System Status Screen is shown below, as it appears on the touchscreen
interface.
6. Commissioning
Checks that are required on first power up
How to set the real time clock and the display language
How to set up users and access levels
How to connect to the web server interface
How to connect to Touchpoint Pro using the PC Configuration Software
For systems ordered with a default configuration, how to check the
configuration and set site specific tags
How to configure input / output modules
How to configure individual input / output channels and program the cause
and effect matrix