Examples - Danfoss VLT AutomationVTDrive FC322 Design Manual

Hide thumbs Also See for VLT AutomationVTDrive FC322:
Table of Contents

Advertisement

Automation VT Drive FC322 Design Guide

7.5 Examples

7.5.1 Writing a Parameter Value
Change par. 4-14
Motor Speed High Limit [Hz]
to 100 Hz.
Write the data in EEPROM.
Motor Speed High Limit
PKE = E19E Hex - Write single word in par. 4-14
[Hz]
IND = 0000 Hex
PWEHIGH = 0000 Hex
PWELOW = 03E8 Hex - Data value 1000, corresponding to 100 Hz, see
Conversion.
Motor Speed High Limit [Hz]
Note: par. 4-14
is a single word, and the
parameter command for write in EEPROM is "E". Parameter number 4-14
is 19E in hexadecimal.
The response from the slave to the master will be:
7.5.2 Reading a Parameter Value
Read the value in par. 3-41
Ramp 1 Ramp Up Time
PKE = 1155 Hex - Read parameter value in par. 3-41
Ramp 1 Ramp Up
Time
IND = 0000 Hex
PWEHIGH = 0000 Hex
PWELOW = 0000 Hex
If the value in par. 3-41
Ramp 1 Ramp Up Time
is 10 s, the response from
the slave to the master will be:
NB!
3E8 Hex corresponds to 1000 decimal. The conversion index for par. 3-41
Unsigned 32
Par. 3-41 is of the type
.
MG.20.X1.22 - VLT
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20783-Danfoss-131X8145-VLT-Automation-VT-Drive-VFD-FC322-460V-.5-HP.aspx
7 RS-485 Installation and Set-up
The telegram will look like this:
Ramp 1 Ramp Up Time
is -2, i.e. 0.01.
®
is a registered Danfoss trademark
7
209

Advertisement

Table of Contents
loading

Table of Contents