Danfoss VLT AutomationVTDrive FC322 Design Manual page 33

Hide thumbs Also See for VLT AutomationVTDrive FC322:
Table of Contents

Advertisement

2 Introduction to VLT Automation VT Drive
2.8.9 Programming Order
Function
Par. no.
1) Make sure the motor runs properly. Do the following:
2
Set the drive to control the motor based on drive output fre-
0-02
quency.
Set the motor parameters using nameplate data.
1-2*
Run Automatic Motor Adaptation.
1-29
2) Check that the motor is running in the right direction.
Press the "Hand On" LCP key and the ^ key to make the
motor turn slowly. Check that the motor runs in the correct
direction.
3) Make sure the frequency converter limits are set to safe values
Check that the ramp settings are within capabilities of the
3-41
drive and allowed application operating specifications.
3-42
Prohibit the motor from reversing (if necessary)
4-10
Set acceptable limits for the motor speed.
4-12
4-14
4-19
Switch from open loop to closed loop.
1-00
4) Configure the feedback to the PID controller.
Set up Analog Input 54 as a feedback input.
20-00
Select the appropriate reference/feedback unit.
20-12
5) Configure the setpoint reference for the PID controller.
Set acceptable limits for the setpoint reference.
3-02
3-03
Set up Analog Input 53 as Reference 1 Source.
3-15
6) Scale the analog inputs used for setpoint reference and feedback.
Scale Analog Input 53 for the pressure range of the potenti-
6-10
ometer (0 - 10 Bar, 0 - 10 V).
6-11
6-14
6-15
Scale Analog Input 54 for pressure sensor (0 - 10 Bar, 4 - 20
6-22
mA)
6-23
6-24
6-25
7) Tune the PID controller parameters.
Adjust the drive's Closed Loop Controller, if needed.
20-93
20-94
8) Finished!
Save the parameter setting to the LCP for safe keeping
0-50
32
MG.20.X1.22 - VLT
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20783-Danfoss-131X8145-VLT-Automation-VT-Drive-VFD-FC322-460V-.5-HP.aspx
Automation VT Drive FC322 Design Guide
Setting
Hz
[1]
As specified by motor name plate
Enable complete AMA
[1] and then run the AMA function.
If the motor runs in the wrong direction, remove power
temporarily and reverse two of the motor phases.
60 sec.
60 sec.
Depends on motor/load size!
Also active in Hand mode.
Clockwise
[0]
10 Hz,
Motor min speed
Motor max speed
50 Hz,
50 Hz,
Drive max output frequency
Closed Loop
[3]
Analog input 54
[2] (default)
Bar
[71]
0 Bar
10 Bar
Analog input 53
[1] (default)
0 V
10 V (default)
0 Bar
10 Bar
4 mA
20 mA (default)
0 Bar
10 Bar
See Optimization of the PID Controller, below.
All to LCP
[1]
®
is a registered Danfoss trademark

Advertisement

Table of Contents
loading

Table of Contents