8 Troubleshooting
Alarm Word and Extended Status Word
Bit
Hex
Dec
Alarm Word
0
00000001
1
Brake Check
1
00000002
2
Pwr. Card Temp
2
00000004
4
Earth Fault
3
00000008
8
Ctrl.Card Temp
4
00000010
16
Ctrl. Word TO
5
00000020
32
Over Current
6
00000040
64
Torque Limit
7
00000080
128
Motor Th Over
8
00000100
256
Motor ETR Over
9
00000200
512
Inverter Overld.
10
00000400
1024
DC under Volt
11
00000800
2048
DC over Volt
12
00001000
4096
Short Circuit
13
00002000
8192
Inrush Fault
14
00004000
16384
Mains ph. Loss
15
00008000
32768
AMA Not OK
16
00010000
65536
Live Zero Error
17
00020000
131072
Internal Fault
18
00040000
262144
Brake Overload
19
00080000
524288
U phase Loss
20
00100000
1048576
V phase Loss
8
21
00200000
2097152
W phase Loss
22
00400000
4194304
Fieldbus Fault
23
00800000
8388608
24 V Supply Low
24
01000000
16777216
Mains Failure
25
02000000
33554432
1.8V Supply Low
26
04000000
67108864
Brake Resistor
27
08000000
134217728
Brake IGBT
28
10000000
268435456
Option Change
29
20000000
536870912
Drive Initialised
30
40000000
1073741824
Safe Stop
Table 8.2: Description of Alarm Word, Warning Word and Extended Status Word
The alarm words, warning words and extended status words can be read out via serial bus or optional fieldbus for diagnosis. See also par. 16-90
Word
Warning Word
Ext. Status Word
, par. 16-92
and par. 16-94
234
MG.20.X1.22 - VLT
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20783-Danfoss-131X8145-VLT-Automation-VT-Drive-VFD-FC322-460V-.5-HP.aspx
Automation VT Drive FC322 Design Guide
Warning Word
Extended Status Word
Brake Check
Ramping
Pwr. Card Temp
AMA Running
Earth Fault
Start CW/CCW
Ctrl.Card Temp
Slow Down
Ctrl. Word TO
Catch Up
Over Current
Feedback High
Torque Limit
Feedback Low
Motor Th Over
Output Current High
Motor ETR Over
Output Current Low
Inverter Overld.
Output Freq High
DC under Volt
Output Freq Low
DC over Volt
Brake Check OK
DC Voltage Low
Braking Max
DC Voltage High
Braking
Mains ph. Loss
Out of Speed Range
No Motor
OVC Active
Live Zero Error
10V Low
Brake Overload
Brake Resistor
Brake IGBT
Speed Limit
Fieldbus Fault
24V Supply Low
Mains Failure
Current Limit
Low Temp
Voltage Limit
Unused
Unused
Unused
.
®
is a registered Danfoss trademark
Alarm