Automation VT Drive FC322 Design Guide
5.11.2 Use of EMC-Correct Cables
Danfoss recommends braided screened/armoured cables to optimise EMC immunity of the control cables and the EMC emission from the motor cables.
The ability of a cable to reduce the in- and outgoing radiation of electric noise depends on the transfer impedance (Z
designed to reduce the transfer of electric noise; however, a screen with a lower transfer impedance (Z
higher transfer impedance (Z
).
T
Transfer impedance (Z
) is rarely stated by cable manufacturers but it is often possible to estimate transfer impedance (Z
T
design of the cable.
Transfer impedance (Z
) can be assessed on the basis of the following factors:
T
-
The conductibility of the screen material.
-
The contact resistance between the individual screen conductors.
-
The screen coverage, i.e. the physical area of the cable covered by the screen - often stated as a percentage value.
-
Screen type, i.e. braided or twisted pattern.
a.
Aluminium-clad with copper wire.
b.
Twisted copper wire or armoured steel wire cable.
c.
Single-layer braided copper wire with varying percentage screen
coverage.
This is the typical Danfoss reference cable.
d.
Double-layer braided copper wire.
e.
Twin layer of braided copper wire with a magnetic, screened/
armoured intermediate layer.
f.
Cable that runs in copper tube or steel tube.
g.
Lead cable with 1.1 mm wall thickness.
MG.20.X1.22 - VLT
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20783-Danfoss-131X8145-VLT-Automation-VT-Drive-VFD-FC322-460V-.5-HP.aspx
5 How to Install
). The screen of a cable is normally
T
) value is more effective than a screen with a
T
) by assessing the physical
T
®
is a registered Danfoss trademark
5
185

Advertisement

Table of Contents
loading

Table of Contents