Automation VT Drive FC322 Design Guide
Bit 01 = '1': The frequency converter is ready for operation but the coasting command is active via the digital inputs or via serial communication.
Bit 02, Coasting stop:
Bit 02 = '0': The frequency converter releases the motor. Bit 02 = '1': The frequency converter starts the motor with a start command.
Bit 03, No error/trip:
Bit 03 = '0' : The frequency converter is not in fault mode. Bit 03 = '1': The frequency converter trips. To re-establish operation, enter [Reset].
Bit 04, No error/error (no trip):
Bit 04 = '0': The frequency converter is not in fault mode. Bit 04 = "1": The frequency converter shows an error but does not trip.
Bit 05, Not used:
Bit 05 is not used in the status word.
Bit 06, No error / triplock:
Bit 06 = '0': The frequency converter is not in fault mode. Bit 06 = "1": The frequency converter is tripped and locked.
Bit 07, No warning/warning:
Bit 07 = '0': There are no warnings. Bit 07 = '1': A warning has occurred.
Bit 08, Speed≠ reference/speed = reference:
Bit 08 = '0': The motor is running but the present speed is different from the preset speed reference. It might e.g. be the case when the speed ramps
up/down during start/stop. Bit 08 = '1': The motor speed matches the preset speed reference.
Bit 09, Local operation/bus control:
Bit 09 = '0': [STOP/RESET] is activate on the control unit or
Local control
converter via serial communication. Bit 09 = '1' It is possible to control the frequency converter via the fieldbus/ serial communication.
Bit 10, Out of frequency limit:
Bit 10 = '0': The output frequency has reached the value in par. 4-11
= "1": The output frequency is within the defined limits.
Bit 11, No operation/in operation:
Bit 11 = '0': The motor is not running. Bit 11 = '1': The frequency converter has a start signal or the output frequency is greater than 0 Hz.
Bit 12, Drive OK/stopped, autostart:
Bit 12 = '0': There is no temporary over temperature on the inverter. Bit 12 = '1': The inverter stops because of over temperature but the unit does not
trip and will resume operation once the over temperature stops.
Bit 13, Voltage OK/limit exceeded:
Bit 13 = '0': There are no voltage warnings. Bit 13 = '1': The DC voltage in the frequency converter's intermediate circuit is too low or too high.
Bit 14, Torque OK/limit exceeded:
Bit 14 = '0': The motor current is lower than the torque limit selected in par. 4-18
Limit
is exceeded.
Bit 15, Timer OK/limit exceeded:
Bit 15 = '0': The timers for motor thermal protection and thermal protection are not exceeded 100%. Bit 15 = '1': One of the timers exceeds 100%.
MG.20.X1.22 - VLT
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20783-Danfoss-131X8145-VLT-Automation-VT-Drive-VFD-FC322-460V-.5-HP.aspx
7 RS-485 Installation and Set-up
in par. 3-13
Reference Site
is selected. You cannot control the frequency
Motor Speed Low Limit [RPM]
or par. 4-13
Motor Speed High Limit [RPM]
Current Limit
. Bit 14 = '1': The torque limit in par. 4-18
®
is a registered Danfoss trademark
7
. Bit 10
Current
227