Table of Contents

Advertisement

Automation VT Drive FC322 Design Guide
3.
Then reapply 24 V DC to terminal 37. The test step is passed if the motor remains in the coasted state, and the mechanical brake (if connected)
remains activated.
4.
Then send Reset signal (via Bus, Digital I/O, or [Reset] key). The test step is passed if the motor becomes operational again.
5.
The commissioning test is passed if all four test steps are passed.
MG.20.X1.22 - VLT