7 RS-485 Installation and Set-up
Bit 13/14, Selection of set-up:
Use bits 13 and 14 to choose from the four menu set-ups according to
the shown table: .
Multi Set-Ups
The function is only possible when
is selected in
par. 0-10
Active Set-up
.
Bit 15 Reverse:
Bit 15 = '0': No reversing. Bit 15 = '1': Reversing. In the default setting, reversing is set to digital in par. 8-54
only when Ser. communication, Logic or or Logic and is selected.
7.11.2 Status Word According to FC Profile (STW) (par. 8-10
7
Bit
Bit = 0
00
Control not ready
01
Drive not ready
02
Coasting
03
No error
04
No error
05
Reserved
06
No error
07
No warning
Speed ≠ reference
08
09
Local operation
10
Out of frequency limit
11
No operation
12
Drive OK
13
Voltage OK
14
Torque OK
15
Timer OK
Explanation of the Status Bits
Bit 00, Control not ready/ready:
Bit 00 = '0': The frequency converter trips. Bit 00 = '1': The frequency converter controls are ready but the power component does not necessarily receive
any power supply (in case of external 24 V supply to controls).
Bit 01, Drive ready:
226
MG.20.X1.22 - VLT
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20783-Danfoss-131X8145-VLT-Automation-VT-Drive-VFD-FC322-460V-.5-HP.aspx
Automation VT Drive FC322 Design Guide
Set-up
Bit 14
Bit 13
1
0
0
2
0
1
3
1
0
4
1
1
NB!
Make a selection in par. 8-55
Set-up Select
to define
how Bit 13/14 gates with the corresponding function
on the digital inputs.
Reversing Select
. Bit 15 causes reversing
Control Profile
= FC profile)
Bit = 1
Control ready
Drive ready
Enable
Trip
Error (no trip)
-
Triplock
Warning
Speed = reference
Bus control
Frequency limit OK
In operation
Stopped, auto start
Voltage exceeded
Torque exceeded
Timer exceeded
®