2.8.8 Example of Closed Loop PID Control
The following is an example of a Closed Loop Control for a booster pump application:
In a water distribution system, the pressure is to be maintained at a constant value. The desired pressure (setpoint) is set between 0 and 10 Bar using
a 0-10 volt potentiometer or can be set by a parameter. The pressure sensor has a range of 0 to 10 Bar and uses a two-wire transmitter to provide a
4-20 mA signal. The output frequency range of the drive is 10 to 50 Hz.
1. Start/Stop via switch connected between terminals 12 (+24 V) and 18.
2. Pressure reference via a potentiometer (0-10 Bar, 0-10 V) connected
to terminals 50 (+10 V), 53 (input) and 55 (common).
3. Pressure feedback via transmitter (0-10 Bar, 4-20 mA) connected to
terminal 54. Switch S202 behind the Local Control Panel set to ON
(current input).