3.7.1 Installation of Duct Cooling Kit in Rittal Enclosures
This section deals with the installation of IP00 / chassis enclosed frequency converters with duct work cooling kits in Rittal enclosures. In addition to the
enclosure a 200 mm base/plinth is required.
Illustration 3.28: Installation of IP00 in Rittal TS8 enclosure.
The minimum enclosure dimension is:
•
D3 and D4 frame: Depth 500 mm and width 600 mm.
•
E2 frame: Depth 600 mm and width 800 mm.
MG.20.X1.22 - VLT
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com