5 How to Install
Frequency converter:
Max. fuse size:
200-240 V
K25-K75
1
10A
1K1-2K2
20A
1
3K0
30A
1
3K7
1
30A
5K5
50A
1
7K5
63A
1
11K
1
63A
15K
80A
1
18K5
125A
1
22K
1
125A
30K
160A
1
5
37K
200A
1
45K
1
250A
380-480 V
K37-1K5
1
10A
2K2-4K0
20A
1
5K5-7K5
30A
1
11K
63A
1
15K
63A
1
18K
63A
1
22K
1
63A
30K
80A
1
37K
100A
1
45K
1
125A
55K
160A
1
75K
250A
1
90K
1
250A
Table 5.4: Non UL fuses 200 V to 480 V
1) Max. fuses - see national/international regulations for selecting an applicable fuse size.
Danfoss PN
Bussmann
20220
170M4017
20221
170M6013
Table 5.5: Additional Fuses for Non-UL Applications, E enclosures, 380-480 V
146
MG.20.X1.22 - VLT
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20783-Danfoss-131X8145-VLT-Automation-VT-Drive-VFD-FC322-460V-.5-HP.aspx
Automation VT Drive FC322 Design Guide
Voltage:
Type:
200-240 V
type gG
200-240 V
type gG
200-240 V
type gG
200-240 V
type gG
200-240 V
type gG
200-240 V
type gG
200-240 V
type gG
200-240 V
type gG
200-240 V
type gG
200-240 V
type gG
200-240 V
type gG
200-240 V
type aR
200-240 V
type aR
380-480 V
type gG
380-480 V
type gG
380-480 V
type gG
380-480 V
type gG
380-480 V
type gG
380-480 V
type gG
380-480 V
type gG
380-480 V
type gG
380-480 V
type gG
380-480 V
type gG
380-480 V
type gG
380-480 V
type aR
380-480 V
type aR
Ferraz
Siba
6.9URD31D08A0700
20 610 32.700
6.9URD33D08A0900
20 630 32.900
®
is a registered Danfoss trademark