Automation VT Drive FC322 Design Guide
Such chemical reactions will rapidly affect and damage the electronic components. In such environments, mount the equipment in a cabinet with fresh
air ventilation, keeping aggressive gases away from the frequency converter.
An extra protection in such areas is a coating of the printed circuit boards, which can be ordered as an option.
NB!
Mounting frequency converters in aggressive environments increases the risk of stoppages and considerably reduces the life of the
converter.
Before installing the frequency converter, check the ambient air for liquids, particles, and gases. This is done by observing existing installations in this
environment. Typical indicators of harmful airborne liquids are water or oil on metal parts, or corrosion of metal parts.
Excessive dust particle levels are often found on installation cabinets and existing electrical installations. One indicator of aggressive airborne gases is
blackening of copper rails and cable ends on existing installations.
NB!
D and E enclosures have a stainless steel back-channel option to provide additional protection in aggressive environments. Proper ventilation is still
required for the internal components of the drive. Contact Danfoss for additional information.

2.4 Vibration and shock

The frequency converter has been tested according to the procedure based on the shown standards:
The frequency converter complies with requirements that exist for units mounted on the walls and floors of production premises, as well as in panels
bolted to walls or floors.
IEC/EN 60068-2-6:
Vibration (sinusoidal) - 1970
IEC/EN 60068-2-64:
Vibration, broad-band random
2.5 Advantages
2.7.1 Why use a Frequency Converter for Controlling Fans and Pumps?
A frequency converter takes advantage of the fact that centrifugal fans and pumps follow the laws of proportionality for such fans and pumps. For further
information see the text
The Laws of Proportionality
.
2.7.2 The Clear Advantage - Energy Savings
The very clear advantage of using a frequency converter for controlling the speed of fans or pumps lies in the electricity savings.
When comparing with alternative control systems and technologies, a frequency converter is the optimum energy control system for controlling fan and
pump systems.
MG.20.X1.22 - VLT
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20783-Danfoss-131X8145-VLT-Automation-VT-Drive-VFD-FC322-460V-.5-HP.aspx
2 Introduction to VLT Automation VT Drive
®
is a registered Danfoss trademark
2
19

Advertisement

Table of Contents
loading

Table of Contents