6 Application Examples

6.1.11 Fixed Variable Speed Pump Wiring Diagram

6

6.1.12 Lead Pump Alternation Wiring Diagram

Every pump must be connected to two contactors (K1/K2 and K3/K4) with a mechanical interlock. Thermal relays or other motor protection devices must
be applied according to local regulation and/or individual demands.
RELAY 1 (R1) and RELAY 2 (R2) are the built-in relays in the frequency converter.
When all relays are de-energized, the first built in relay to be energized will cut in the contactor corresponding to the pump controlled by the
relay. E.g. RELAY 1 cuts in contactor K1, which becomes the lead pump.
K1 blocks for K2 via the mechanical interlock preventing mains to be connected to the output of the frequency converter (via K1).