3 VLT Automation VT Drive Selection
Warning Dual supply
NB!
The label MUST be placed on the LCP frame as shown (UL approved).
3
How to add the MCO 101 option:
The power to the frequency converter must be disconnected.
The power to the live part connections on relay terminals must be disconnected.
Remove the LCP, the terminal cover and the cradle from the FC322.
Fit the MCO 101 option in slot B.
Connect the control cables and relief the cables by the enclosed cable strips.
Various systems must not be mixed.
Fit the extended cradle and terminal cover.
Replace the LCP
Connect power to the frequency converter.
Wiring the Terminals
Do not combine low voltage parts and PELV systems.
90
MG.20.X1.22 - VLT