6 Application Examples
Preset Reference
Set Preset reference 0 to first preset speed (par. 3-10
60%
Set preset reference 1 to second preset speed (par. 3-10
Preset Reference
SL Controller Timer
Set the timer 0 for constant running speed in par. 13-20
Set Event 1 in par. 13-51
SL Controller Event
[1] to
True
[1]
Set Event 2 in par. 13-51
SL Controller Event
[2] to
On Reference
SL Controller Event
Time Out 0
Set Event 3 in par. 13-51
[3] to
[30]
Set Event 4 in par. 13-51
SL Controller Event
[1] to
False
[0]
Set Action 1 in par. 13-52
SL Controller Action
[1] to
Select preset 0
SL Controller Action
Start Timer 0
Set Action 2 in par. 13-52
[2] to
Set Action 3 in par. 13-52
SL Controller Action
[3] to
Select preset 1
Set Action 4 in par. 13-52
SL Controller Action
[4] to
No Action
[1]
6
Set the Smart Logic Control in par. 13-00
SL Controller Mode
to ON.
Start / stop command is applied on terminal 18. If stop signal is applied the frequency converter will ramp down and go into free mode.
190
MG.20.X1.22 - VLT
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20783-Danfoss-131X8145-VLT-Automation-VT-Drive-VFD-FC322-460V-.5-HP.aspx
Automation VT Drive FC322 Design Guide
Maximum Reference
[0]) in percentage of Max reference speed (par. 3-03
[1] Ex.: 0 % (zero).
[0]. Ex.: 2 sec.